What the example does
The office borefield is coupled to a heat pump model: the heat pump's efficiency follows the fluid temperature that comes out of the field, and its ground heat drives the field. The system runs for 25 years in one-hour steps, and the field is sized with the heat pump in the loop.
Inputs
| Input | Value |
|---|---|
| Field | 16 boreholes, 4 × 4 rectangle, spacing 6.0 × 6.0 m |
| Boreholes | length 150.0 m, top 4.0 m below the surface, diameter 140 mm |
| Construction | single U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K) |
| Ground | thermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m² |
| Fluid and flow | 25 % monopropylene glycol, 0.50 l/s per borehole |
| Loads | monthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h |
| Heat pump | seasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling |
| Design limits | mean fluid temperature between −3.0 °C and 20.0 °C |
| Period | 25 years |
| System | borefield + heat pump model (FMI 2.0 co-simulation unit): COP = 0.5 T_sink / (T_sink − T_source), sink 35 °C; building heating 184 MWh/a |
| Run | 25 years, hybrid long-term mode, communication step 1 h |
Run the example in BoreTherm
- Open Advanced analysis → Co-simulation → System: the blocks and their connections.
- Confirm that you trust the heat pump model when BoreTherm asks.
- On Co-simulation → Settings, choose the period and the long-term mode, and run the co-simulation.
- Co-simulation → Results: every signal of the run; Size with the co-simulation finds the length.
How the coupled run works
- Building loadThe building's heating demand drives the heat pump.
- Heat pump modelThe COP depends on the source temperature: a colder field means more electricity and less heat from the ground.
- BorefieldBoreTherm calculates the field outlet temperature from the ground heat.
- FeedbackThe loop is closed explicitly once per communication step (1 h).
- Long termDetailed years alternate with a faster approximation in between.
- SizingThe coupled system is rerun at other lengths.
The example in BoreTherm
Calculated results
Calculated with BoreTherm for every variant of the example. Displayed values are rounded.
| Coupled metric | Value |
|---|---|
| Mode | hybrid |
| Communication step [s] | 3,600.000 |
| Tf min [°C] | -1.997 |
| Tf max [°C] | 9.165 |
| Limits met | Yes |
| Required H [m] | 138.299 |
| Required total length [m] | 2,212.785 |
| FMU bytes | 42541291 |
Temperatures by variant
| Variant | Boreholes | Length H [m] | Tf min [°C] | Tf max [°C] | Rb* [m K/W] | Pump [W] | Design limits |
|---|---|---|---|---|---|---|---|
| office, fixed SPF | 16 | 150.000 | -2.413 | 16.026 | 0.1194 | 3,033.2 | within limits |
| co-simulation, 150 m | — | — | -1.997 | 9.165 | — | — | within limits |
| co-simulation, sized | — | — | -2.998 | 8.909 | — | — | within limits |
What the example shows
With the heat pump in the loop the minimum is −2.00 °C at 150 m, and coupled sizing finds 138.3 m: the heat pump draws less from a colder field than a fixed seasonal factor assumes. The years between the detailed ones follow the hybrid approximation.
The heat pump model is a small demonstration model. Co-simulation with other tools' models follows the FMI standard; check every model before relying on it.