Ground response
Finite-line-source g-functions describe borefield interaction. Ground layers, temperature gradients and groundwater assumptions set the context.
Explore the reference comparisons, model conventions and published methods behind BoreTherm’s engineering calculations.
Month-end mean fluid temperature, base and peak loads, against an independent open-source sizing tool.
Each comparison below names the kind of reference, the quantity compared and the largest difference found. The worked examples were recalculated with BoreTherm in October 2026.
Agreement with a reference shows that the method is implemented as published. It does not replace a review of the inputs of a real project.
| Reference | Compared quantity | Reported agreement |
|---|---|---|
| Independent software | ||
| Open-source g-function library | g-functions, 10 layouts, all exact methods | 5·10⁻¹¹ |
| Open-source sizing tool | Month-end mean fluid temperature, base and peak | ≤ 0.130 K |
| Open-source sizing tool | Hourly fluid temperature | ≤ 0.016 K |
| Open-source sizing tool | Required borehole length | ≤ 0.06 % |
| Published results | ||
| Published software manual, worked example | 48 monthly temperatures · required length | 0.15 K · 0.3 % |
| Published software reference values | Rb* against flow rate | ≤ 0.09 % |
| Ahmadfard & Bernier [9] | Seven inter-model sizing cases | ≤ 1.3 % |
| Beier et al. [4] | TRT conductivity, laboratory sandbox | 1.8 % |
| Design handbooks: Kavanaugh & Rafferty, Chiasson, Bonin, Laloui & Rotta Loria | Nine worked examples: borehole resistance, pump head, heat pump selection, required length, energy pile | Rb (single U) ≤ 0.4 % · pump head ≤ 1.9 % where the book calculates the loop loss · lengths −12 % to +10 % against the handbook design equations; every difference explained per example |
| Independent numerics | ||
| Finite-volume solution | Layered g-function, two / three layers | 0.58 % / 2.23 % |
| Time-domain evaluation | Moving finite line source (groundwater) | 4·10⁻¹² |
| Point-source quadrature | Inclined boreholes | 10⁻¹⁴ |
| Stehfest-inverted analytic solution | Short-time radial borehole model | 2.6·10⁻⁴ |
| Synthetic TRT | Recovered λ · Rb* | 1 % · 2 % |
Finite-line-source g-functions describe borefield interaction. Ground layers, temperature gradients and groundwater assumptions set the context.
Multipole borehole resistance, convection and flow calculations connect the ground response to fluid temperatures and pressure loss.
Monthly base and peak loads, or hourly series, are superposed over the design horizon. Peak and aggregation conventions matter.
Sizing searches for the length that meets the stated limits. Studies, uncertainty and higher-detail models explore how assumptions change that result.
These publications provide methods and reference data. They do not certify every implementation or design that uses them.
Eskilson, P. (1987). Doctoral thesis, Lund University.
Long-term ground response and g-functions.
Cimmino, M. & Bernier, M. (2014). International Journal of Heat and Mass Transfer, 70, 641–650.
Finite-line-source segmentation and borefield interaction.
Claesson, J. & Hellström, G. (2011). HVAC&R Research, 17(6), 895–911.
Borehole thermal resistance and internal heat transfer.
Beier, R.A., Smith, M.D. & Spitler, J.D. (2011). Geothermics, 40(1), 79–85.
Measured laboratory TRT with independent material properties (example 06).
Prieto, C. & Cimmino, M. (2021). Journal of Building Performance Simulation, 14(4), 446–460.
Equivalent-borehole clustering for large fields.
Cullin, J.R. & Spitler, J.D. (2011). Geothermics, 40(2), 144–156.
Time discretisation and load aggregation.
Diersch, H.-J.G., Bauer, D., Heidemann, W., Rühaak, W. & Schätzl, P. (2011). Computers & Geosciences, 37(8), 1122–1135.
Coupled formation and borehole heat exchanger equations.
Kirschstein, X., Ohagen, M., Reber, J., Sass, I. & Hübler, C. (2025). European Geothermal Congress.
Measured-case comparison of simplified borefield models and co-simulation.
Ahmadfard, M. & Bernier, M. (2019). Renewable and Sustainable Energy Reviews, 110, 247–265.
Inter-model sizing cases used for validation.
It is the reported maximum difference for the specified cases of the open-source sizing tool after matching the documented comparison conventions. It is not an uncertainty bound on a real site, where ground and load assumptions also affect the result.
Read the project description and input assumptions, then compare the results and design variants on the example page. Use the discussion and warning log to identify what the model does and does not establish.
Ground properties, hydraulic assumptions, boundary and mesh choices, temperature limits and operating loads must suit the project. A qualified engineer must review a real design, including site and permitting requirements.