The one idea: the same service, priced over the whole period
Every enabled variant must deliver the same useful heat, hot water and cold to the building. Each one needs a different amount of final energy for it, and each one has a different investment, service life and maintenance. BoreTherm turns all of it into one number per variant: the annual full cost, the annuity of all discounted cash flows over the period (VDI 2067 style).
a = i / (1 − (1 + i)−T)A = a · Σ CFt (1 + i)−tLCOH = (A − Acold) / QheatSPF = Qheat / Welfuel = Qheat / ηTerms: i interest rate, T period in years, CFt cash flow of year t, NPV net present value (the sum of the discounted cash flows). COP (coefficient of performance): heat / electricity of a heat pump at one operating point; SPF (seasonal performance factor): the same over the year; SEER and EER: cold / electricity over the year and at one point; η: efficiency of a boiler or a district-heating substation. JAZ: the seasonal performance factor after the guideline VDI 4650; B0/W35: brine 0 °C, heating water 35 °C. DHW: domestic hot water. BHE (borehole heat exchanger): the ground-source variant.
The workflow
The comparison needs building loads. Before it starts, decide on Design › Heat pump › Setup how the heat pump enters the borefield calculation; that also decides which heat pump the ground-source variant uses. The comparison is calculated with Calculation › Calculate.
- Borefield costs: check the estimate. Its net total is the borefield investment (service life 50 years); it is recalculated from the current design every time, so a different length changes the investment.
- Heating-system comparison: tick Include system comparison when calculating; set the period, interest, gross or net prices, residual value, KfW grant estimate, CO₂ price scenario and synthetic climate. The variant table holds the net equipment investment, life, COP or efficiency, auxiliary electricity, operation and the chiller SEER of each variant; Advanced assumptions… shows the full specification (heat pump models, tariffs, grants, cooling allocation). Every datum of the data set carries its value, unit, validity dates, source and status.
- Enter qualitative scores and knock-outs if needed (noise, space, permits, drilling risk, price exposure). A knock-out removes a variant from the lowest-cost marker; scores never change the costs.
- Calculate (Calculation › Calculate or the button Calculate comparison) and read Results › System comparison with its warnings. Economic tornado and LCOH and SPF versus length answer the next questions.
How the calculation works
Ground-source variant. BoreTherm uses the borefield simulation of the project. If the variant’s cooling differs from the design (passive instead of active cooling, or a separate chiller), the borefield is simulated again for that cooling. Month by month (hour by hour with hourly loads) the heat pump sees the brine leaving the field, Tout = Tf − Q / (2 ṁ cp) (Tf: mean fluid temperature of the borehole, the mean of inlet and outlet; Q: heat taken from the ground; ṁ cp: mass flow × specific heat of the brine), as its source and the heating-curve flow temperature (domestic hot water: its own temperature) as its sink. The COP comes from the heat pump model; load above the capacity, or brine below the minimum source temperature, goes to an electric backup at COP 1. The source pump runs its hours. Passive cooling is used while the brine for the peak injection case stays at or below the passive limit (16 °C by default); above it the machine cools actively with its EER.
Air/water and hybrid. Hour by hour from the synthetic outdoor temperature: COP(outdoor, flow), the capacity of the machine, hot water first, backup heater for the rest. Below the bivalence point (−3 °C by default) the hybrid’s gas boiler covers what its heat pump cannot. Boilers and district heating need heat / η of fuel plus auxiliary electricity. A variant that cannot cool gets an air-cooled chiller (SEER 3.5) so the service stays equal.
The theory behind the result
Climate, heating curve and COP
The comparison does not use measured weather. It builds a seeded synthetic year: a seasonal cosine around the mean of the climate preset, a daily cycle (± 4 K, warmest at 15 h) and an autocorrelated day-to-day weather (σ 3 K). The heating curve gives the flow temperature from the outdoor temperature, linear between the heating limit (flow = return temperature) and the design outdoor temperature (flow = design flow temperature).
Cash flows and the annual full cost
Investments are paid at t = 0 and again after each service life inside the period; energy and operation at the end of every year t = 1…T; a grant at t = 0; the residual value of the last installation (its unused linear life) is credited at t = T. Every amount is discounted at its own time, summed to the NPV and turned into the annual full cost with the annuity factor a. Each cost group gets its own annuity, which is what the chart below shows. Prices are real (EUR 2026) unless you choose nominal prices and enter consistent paths.
How each result is derived
Ground-source variant of the example (office, 16 × 150 m, fixed SPF mode, passive cooling), data set DE 2026-10 (2026-10-18), gross, real prices, EUR.
| Result | How BoreTherm derives it | Example |
|---|---|---|
| Useful heat and cold | building loads; monthly loads are spread over hours with the load generator; multiyear loads are averaged | heat 208,000 kWh/a (DHW 8,000), cold 45,000 kWh/a |
| Ground-source electricity | month by month: COP(field outlet, heating-curve flow), capacity share, backup at COP 1, source pump; passive cooling: the pump only | heating 44,605 kWh/a (pump 13,363 in total), cooling 7,297 kWh/a |
| SPF, SEER | heat / heating electricity (with backup and source pump); cold / cooling electricity | SPF 4.66, SEER 6.17 |
| JAZ after VDI 4650 | COPB0/W35 · FΔϑ · Fϑ / FP, hot water by eq. 5, overall eq. 13; ϑB,min = lowest monthly field outlet | 4.53 (ϑB,min 0.98 °C, FP 1.134) |
| Investment | plant a · Pb at the peak (without the borehole source) + extras + borefield = the net total of Borefield costs; × (1 + VAT) for gross prices | (60,834 + 41,332 + 131,200) × 1.19 = 277,705 € |
| Energy cost | kWh × tariff of the carrier each year (+ CO₂ charge for gas and oil) | 51,902 kWh × 0.28 €/kWh = 14,533 €/a |
| Operation | investment × (fInst + fW+Insp) + hours × labour rate (residential: 0 €/h) | 6,494 €/a, constant in real prices: annuity 6,494 €/a |
| Residual value | unused linear life of the last installation, credited at t = T | borefield 156,128 × (50 − 20) / 50 = 93,677 € → −3,855 €/a |
| Annual full cost | a · NPV, a = i / (1 − (1 + i)−T) | a = 0.0612 (i = 2 %, T = 20 a): 34,154 €/a |
| LCOH | heat: (A − cooling share) / heat; heat + cold: A / (heat + cold); cold: cooling share / cold | 15.4 / 13.5 / 4.5 ct/kWh |
| CO₂ and primary energy | kWh × factor of the carrier at the data date (statutory GModG Anlage 9 / 4; estimate: direct CO₂) | 29.1 t/a statutory, 17.9 t/a estimate, 93 MWh/a |
| Break-even year | first year after which the discounted cumulative cost of the BHE stays below the other variant | gas 2042, air/water: none |
The example in numbers
| Variant | Investment [€] | Annual full cost [€/a] | LCOH heat [ct/kWh] | SPF (heat pump) or η | CO₂ stat. [t/a] | BHE cheaper from |
|---|---|---|---|---|---|---|
| Ground-source HP | 277,705 | 34,154 | 15.4 | 4.66 | 29.1 | — |
| Air/water HP | 187,690 | 31,734 | 13.7 | 4.45 | 32.5 | never |
| Gas boiler | 65,941 | 40,299 | 16.6 | 0.96 | 54.2 | 2042 |
| Oil boiler | 78,383 | 45,292 | 19.0 | 0.93 | 76.6 | 2039 |
| Pellet boiler | 133,785 | 35,502 | 14.3 | 0.90 | 12.0 | 2045 |
| District heating | 59,300 | 41,036 | 16.9 | 0.98 | 45.5 | 2040 |
| Hybrid air HP + gas | 247,395 | 40,269 | 16.6 | — | 36.9 | 2039 |
In this example the air/water heat pump has the lowest annual full cost; the ground-source system costs 2,421 €/a more. By cost group, ground-source minus air/water heat pump [€/a]: capital +17, energy −1,719, operation +3,290, residual value +833. The largest difference is operation: the data set gives the borefield VDI 2067 repair and servicing of 3 % of its investment per year (4,684 €/a here). The ground-source system has the lower energy cost and CO₂ and beats gas, oil, pellets, district heating and the hybrid within the period. The default tariffs and plant costs are illustrative (status “assumption”): replace them, and review the borefield’s operation fractions, before you draw a conclusion.
Fixed SPF or the project’s heat pump
| Ground-source variant | Fixed seasonal efficiency | Temperature-dependent |
|---|---|---|
| Project | office_4x4_example | heat_pump_office_solution |
| Heat pump in the calculation | fixed SPF on Setup; the variant’s generic model | temperature-dependent; Beta 60 × 2 (Setup) |
| Borehole length, borefield net total | 150 m, 131,200 € | 160.0 m, 138,415 € |
| Coupling passes | none (one pass) | 3, converged yes |
| SPF (simulated) / JAZ (VDI 4650) | 4.66 / 4.53 | 4.71 / 5.13 |
| Electricity [kWh/a] | 51,902 | 51,984 |
| Annual full cost | 34,154 €/a | 34,748 €/a |
In the temperature-dependent case the ground-source variant uses the project’s heat pump (here Beta 60 × 2, 120 kW, minimum brine −8 °C, EER 5.6) and the borefield sized for it. The plant investment of the variant stays the cost curve of the data set; enter the quotation of the machine in the variant table.
Limits to keep in mind
- The climate is synthetic (DE-central: mean 10 °C, amplitude 9 K, design −12 °C), not a test reference year. It drives the air/water COP and the heating curve of every heat pump.
- Default tariffs, plant costs, chiller and district-heating data are illustrative; the data set flags each value with its status and date, and warns when values expire or are older than six months.
- The simulated SPF includes compressor, backup and source pump; it is not the VDI 4650 JAZ, which BoreTherm reports beside it. With monthly loads the brine minimum of the JAZ is a monthly mean (VDI 4650 suggests a weekly mean).
- In the temperature-dependent mode the project’s heat pump model must have a realistic capacity (Setup): a model with small datasheet capacities sends most of the heat to the backup heater and the SPF collapses.
- With fixed seasonal efficiency the borefield temperatures and the comparison’s COP come from different assumptions (a warning says so).
- Grants are off by default; the automatic KfW estimate does not check eligibility. Ecological values are annual values at the data date, not lifetime forecasts; the CO₂ price scenarios change only the variants that burn gas or oil.
- The comparison covers one building. Landlord cost splits, tax credits, refrigerant leakage and DWD weather files are not modelled.
Numbers calculated with BoreTherm. Calculated with boretherm-cli compare. Indicative comparison, not a binding offer.