What the example does
The same office building is placed on nine different borehole patterns: a single borehole, a line, an L-shape, a U-shape, a circle, concentric rings, a hexagonal grid, the 4 × 4 rectangle of the reference design and free coordinates. All variants keep the building loads, the borehole length (150 m) and the design limits. The example shows how the number of boreholes and their arrangement change the fluid temperatures.
Inputs
| Input | Value |
|---|---|
| Field | 16 boreholes, 4 × 4 rectangle, spacing 6.0 × 6.0 m |
| Boreholes | length 150.0 m, top 4.0 m below the surface, diameter 140 mm |
| Construction | single U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K) |
| Ground | thermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m² |
| Fluid and flow | 25 % monopropylene glycol, 0.50 l/s per borehole |
| Loads | monthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h |
| Heat pump | seasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling |
| Design limits | mean fluid temperature between −3.0 °C and 20.0 °C |
| Period | 25 years |
| Variants | single, line (6), L-shape (7), U-shape (10), circle (8), rectangle 4 × 4 (16), custom (16), concentric rings (19), hexagonal (37) |
Run the example in BoreTherm
- Start with File → New from example: the office building on a 4 × 4 field.
- Open Design → Field layout. Choose a pattern under Layout (type, number of boreholes, spacing) and click Regenerate; for free positions, drag boreholes in the plan or type coordinates in the table.
- Press Calculate and read the minimum and maximum mean fluid temperature on Results → Results summary.
- Repeat for the other patterns and compare the temperatures with the design limits of −3 °C and 20 °C.
Why the arrangement matters
Each borehole cools its neighbours. BoreTherm calculates this interaction from the positions of all boreholes: the g-function of the field. The same loads then give different temperatures for every layout.
- PositionsThe pattern generator turns the pattern, the number of boreholes and the spacing into coordinates. Free positions are entered directly.
- Load per metreThe heat pump draws up to 74 kW from the ground in the coldest month. On 16 boreholes of 150 m that is 30.7 W/m; on 6 boreholes it is 81.9 W/m.
- Field g-functionFor every pair of boreholes the finite line source gives the temperature that one causes at the other. Their sum over the field, as a function of time, is the g-function. A compact field (hexagonal, rings) has more neighbours per borehole than a line.
- TemperaturesThe monthly loads and the 6-hour peaks are superposed on the g-function over 25 years. The result is the mean fluid temperature of every month.
The example in BoreTherm
Calculated results
Calculated with BoreTherm for every variant of the example. Displayed values are rounded.
Temperatures by variant
| Variant | Boreholes | Length H [m] | Tf min [°C] | Tf max [°C] | Rb* [m K/W] | Pump [W] | Design limits |
|---|---|---|---|---|---|---|---|
| circle | 8 | 150.000 | -12.461 | 21.603 | 0.1194 | 1,516.6 | limits exceeded |
| concentric rings | 19 | 150.000 | -0.856 | 15.144 | 0.1194 | 3,601.9 | within limits |
| custom | 16 | 150.000 | -2.405 | 16.036 | 0.1194 | 3,033.2 | within limits |
| rectangle 4 × 4 (reference) | 16 | 150.000 | -2.413 | 16.026 | 0.1194 | 3,033.2 | within limits |
| hexagonal | 37 | 150.000 | 3.543 | 12.903 | 0.1194 | 7,014.3 | within limits |
| line | 6 | 150.000 | -16.722 | 25.981 | 0.1194 | 1,137.4 | limits exceeded |
| L-shape | 7 | 150.000 | -13.500 | 23.725 | 0.1194 | 1,327.0 | limits exceeded |
| single borehole | 1 | 150.000 | -129.862 | 106.378 | 0.1194 | 189.6 | limits exceeded |
| U-shape | 10 | 150.000 | -7.257 | 19.779 | 0.1194 | 1,895.7 | limits exceeded |
What the example shows
All layouts carry the same building load. A layout with fewer boreholes therefore has fewer metres and a higher load per metre, which is the main reason for the large differences. Compare layouts together with their total length: these variants show the geometry, they are not equally sized designs. To compare layouts at equal performance, size each one (Size borehole length) or let Optimize search the plot.
At equal total length, a compact layout is warmer in winter than a line only in the long run: in the first years the boreholes hardly see each other, after decades the neighbours' cooling adds up. The g-function contains this growth.