A compact 7 by 3 head pattern demonstrates straight inclined axes. Compare a radial fan, an arc, parallel directional axes and radial outward axes.

21Boreholes
1.63 °CMinimum mean fluid temperature
15.10 °CMaximum mean fluid temperature
4Variants compared
01 / Project

What the example does

Twenty-one borehole heads stand close together in 7 × 3 rows, 1 m by 2 m apart, as on a narrow plot. The boreholes are drilled at an angle so that their lower parts spread out. The example compares a radial fan, an arc, parallel (directional) axes and radial outward axes on the office building load.

Inputs

InputValue
Field21 boreholes, 7 × 3 rectangle, spacing 1.0 × 2.0 m
Boreholeslength 150.0 m, top 0.0 m below the surface, diameter 140 mm, inclined up to 20° from the vertical
Constructionsingle U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K)
Groundthermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m²
Fluid and flow25 % monopropylene glycol, 0.50 l/s per borehole
Loadsmonthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h
Heat pumpseasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling
Design limitsmean fluid temperature between −3.0 °C and 20.0 °C
Period25 years
Variantsradial fan (20° at the edge), arc, all axes in one direction, radial outward

Run the example in BoreTherm

  1. Open Design → Field layout. Under Inclination choose the mode (radial fan, arc, directional, radial) and the tilt; the table shows the tilt and azimuth of every borehole.
  2. Switch the view to 3D to see the axes, and check the clearance warnings: the closest distance between two axes is listed.
  3. Press Calculate and compare the temperatures on Results → Results summary.
02 / How BoreTherm calculates it

Inclined axes in the g-function

An inclined borehole is a straight line source at an angle. Its length is measured along the axis, so the depth of its bottom is shorter than its length. The heads stay where they are; the bottoms move apart, and this reduces the interaction in the long run.

1 Axeshead x, y; tilt θ, azimuth φbottom = head + H (sinθ cosφ, …)2 Segmentseach axis cut into 8 segmentsalong its length3 Distancesbetween all segments of allaxes, in 3D4 Field g-functioninclined finite line sourcessuperposed, uniform wall T5 Ground at mid-depthTm from the vertical depthof the segments6 Temperaturesthe office loads on thefield response, 25 yearsFan: TfMin 1.63 °C, TfMax 15.10 °C (21 × 150 m)
The steps for inclined boreholes. Steps 1 to 3 replace the plan distances of a vertical field.
  1. AxesEach borehole has a tilt from the vertical and an azimuth. In the fan, the tilt grows towards the edge of the field up to 20°; the centre borehole stays vertical.
  2. SegmentsEvery axis is divided into segments, so that the heat flow along it can vary.
  3. DistancesThe response of one segment on another depends on their distance in space. With inclined axes it grows with depth.
  4. Field g-functionThe responses are summed for the boundary condition of a uniform borehole wall temperature.
  5. Ground at mid-depthThe undisturbed temperature uses the vertical depth, not the length.
  6. TemperaturesThe loads are superposed as for a vertical field.
03 / In BoreTherm

The example in BoreTherm

Design → Field layout: the fan in plan; the lines show where the axes go.
Design → Field layout: the fan in plan; the lines show where the axes go.
The same field in 3D: the axes spread out with depth.
The same field in 3D: the axes spread out with depth.
Results → Results summary of the fan.
Results → Results summary of the fan.
04 / Results

Calculated results

Calculated with BoreTherm for every variant of the example. Displayed values are rounded.

Inclined boreholes results plotted from BoreTherm output
Chart of the BoreTherm results in the tables of this section.

Temperatures by variant

VariantBoreholesLength H [m]Tf min [°C]Tf max [°C]Rb* [m K/W]Pump [W]Design limits
arc21150.000-1.58914.7930.11943,981.1within limits
all axes in one direction21150.000-8.10915.5420.11943,981.1limits exceeded
radial fan21150.0001.63115.1030.11943,981.1within limits
radial outward21150.0001.69415.2530.11943,981.1within limits
05 / Discussion

What the example shows

Spreading the axes makes the dense field behave like a larger one: the fan and the radial variant stay above 1.6 °C, while all axes tilted in the same direction keep the boreholes as close as at the surface and reach −8.1 °C. The arc lies between them.

The heads are only 1 to 2 m apart, so BoreTherm warns about clearances near the top. Check these warnings with the driller: deviation during drilling can be larger than the distance. An arc describes the arrangement of straight axes, not a curved borehole.