What the example does
Twenty-one borehole heads stand close together in 7 × 3 rows, 1 m by 2 m apart, as on a narrow plot. The boreholes are drilled at an angle so that their lower parts spread out. The example compares a radial fan, an arc, parallel (directional) axes and radial outward axes on the office building load.
Inputs
| Input | Value |
|---|---|
| Field | 21 boreholes, 7 × 3 rectangle, spacing 1.0 × 2.0 m |
| Boreholes | length 150.0 m, top 0.0 m below the surface, diameter 140 mm, inclined up to 20° from the vertical |
| Construction | single U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K) |
| Ground | thermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m² |
| Fluid and flow | 25 % monopropylene glycol, 0.50 l/s per borehole |
| Loads | monthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h |
| Heat pump | seasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling |
| Design limits | mean fluid temperature between −3.0 °C and 20.0 °C |
| Period | 25 years |
| Variants | radial fan (20° at the edge), arc, all axes in one direction, radial outward |
Run the example in BoreTherm
- Open Design → Field layout. Under Inclination choose the mode (radial fan, arc, directional, radial) and the tilt; the table shows the tilt and azimuth of every borehole.
- Switch the view to 3D to see the axes, and check the clearance warnings: the closest distance between two axes is listed.
- Press Calculate and compare the temperatures on Results → Results summary.
Inclined axes in the g-function
An inclined borehole is a straight line source at an angle. Its length is measured along the axis, so the depth of its bottom is shorter than its length. The heads stay where they are; the bottoms move apart, and this reduces the interaction in the long run.
- AxesEach borehole has a tilt from the vertical and an azimuth. In the fan, the tilt grows towards the edge of the field up to 20°; the centre borehole stays vertical.
- SegmentsEvery axis is divided into segments, so that the heat flow along it can vary.
- DistancesThe response of one segment on another depends on their distance in space. With inclined axes it grows with depth.
- Field g-functionThe responses are summed for the boundary condition of a uniform borehole wall temperature.
- Ground at mid-depthThe undisturbed temperature uses the vertical depth, not the length.
- TemperaturesThe loads are superposed as for a vertical field.
The example in BoreTherm
Calculated results
Calculated with BoreTherm for every variant of the example. Displayed values are rounded.
Temperatures by variant
| Variant | Boreholes | Length H [m] | Tf min [°C] | Tf max [°C] | Rb* [m K/W] | Pump [W] | Design limits |
|---|---|---|---|---|---|---|---|
| arc | 21 | 150.000 | -1.589 | 14.793 | 0.1194 | 3,981.1 | within limits |
| all axes in one direction | 21 | 150.000 | -8.109 | 15.542 | 0.1194 | 3,981.1 | limits exceeded |
| radial fan | 21 | 150.000 | 1.631 | 15.103 | 0.1194 | 3,981.1 | within limits |
| radial outward | 21 | 150.000 | 1.694 | 15.253 | 0.1194 | 3,981.1 | within limits |
What the example shows
Spreading the axes makes the dense field behave like a larger one: the fan and the radial variant stay above 1.6 °C, while all axes tilted in the same direction keep the boreholes as close as at the surface and reach −8.1 °C. The arc lies between them.
The heads are only 1 to 2 m apart, so BoreTherm warns about clearances near the top. Check these warnings with the driller: deviation during drilling can be larger than the distance. An arc describes the arrangement of straight axes, not a curved borehole.