What the example does
The reference design: an office building of about 3,000 m² with 200 MWh heating, 8 MWh hot water and 45 MWh cooling a year, on 16 boreholes of 150 m. BoreTherm calculates 25 years of mean fluid temperature and checks them against the limits of −3 °C and 20 °C. A second variant shortens the boreholes to 100 m.
Inputs
| Input | Value |
|---|---|
| Field | 16 boreholes, 4 × 4 rectangle, spacing 6.0 × 6.0 m |
| Boreholes | length 150.0 m, top 4.0 m below the surface, diameter 140 mm |
| Construction | single U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K) |
| Ground | thermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m² |
| Fluid and flow | 25 % monopropylene glycol, 0.50 l/s per borehole |
| Loads | monthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h |
| Heat pump | seasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling |
| Design limits | mean fluid temperature between −3.0 °C and 20.0 °C |
| Period | 25 years |
| Variants | 150 m (reference); 100 m (undersized) |
Run the example in BoreTherm
- Start with File → New from example.
- Press Calculate.
- Open Results → Mean fluid temperature for the monthly curve and Results → Annual minimum / maximum for the extremes of every year.
- Results → Results summary lists the resistances, the g-function, the pump power and the freezing check.
What Calculate computes
- Ground at mid-depth9 °C at the surface plus 0.06 W/m² over 2.6 W/(m·K) over half the borehole length (75 m): Tm = 10.73 °C.
- Borehole resistanceFrom the single U, the grout and the glycol flow: Rb* = 0.119 m·K/W.
- g-functionThe response of the 4 × 4 field to a constant load per metre, from minutes to 25 years.
- Ground loads153 MWh extracted and 54 MWh injected a year; peaks up to 74 kW (30.7 W/m).
- SuperpositionEach month's load change is a step on the g-function; the peak is superposed at the end of the month. Tf = Tm + ground temperature change + q Rb*.
- Extremes and checksThe coldest month is a January in year 25: the net extraction cools the field every year. The warmest is a July in year 1.
The example in BoreTherm
Calculated results
Calculated with BoreTherm for every variant of the example. Displayed values are rounded.
Temperatures by variant
| Variant | Boreholes | Length H [m] | Tf min [°C] | Tf max [°C] | Rb* [m K/W] | Pump [W] | Design limits |
|---|---|---|---|---|---|---|---|
| 150 m (reference) | 16 | 150.000 | -2.413 | 16.026 | 0.1194 | 3,033.2 | within limits |
| 100 m | 16 | 100.000 | -8.672 | 18.034 | 0.1170 | 2,022.1 | limits exceeded |
What the example shows
The monthly result consists of month-end base temperatures plus the peak pulses. The minimum falls from year to year because the building takes more heat from the ground than it returns in summer. The decline slows down: 0.9 K in the first year, 0.05 K in the last.
The 100 m variant keeps the limits and the loads: BoreTherm reports −8.67 °C and marks the limits as exceeded. The next example finds the length that just meets them.