BoreTherm / Example libraryExample 07 / 23
Worked feature example

Thermal simulation

Calculate 25 years of mean fluid temperature for the 16-borehole office field, export the g-function and examine thermal resistance and temperature limits.

16Boreholes
-2.41 °CMinimum mean fluid temperature
16.03 °CMaximum mean fluid temperature
2Variants compared
01 / Project

What the example does

The reference design: an office building of about 3,000 m² with 200 MWh heating, 8 MWh hot water and 45 MWh cooling a year, on 16 boreholes of 150 m. BoreTherm calculates 25 years of mean fluid temperature and checks them against the limits of −3 °C and 20 °C. A second variant shortens the boreholes to 100 m.

Inputs

InputValue
Field16 boreholes, 4 × 4 rectangle, spacing 6.0 × 6.0 m
Boreholeslength 150.0 m, top 4.0 m below the surface, diameter 140 mm
Constructionsingle U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K)
Groundthermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m²
Fluid and flow25 % monopropylene glycol, 0.50 l/s per borehole
Loadsmonthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h
Heat pumpseasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling
Design limitsmean fluid temperature between −3.0 °C and 20.0 °C
Period25 years
Variants150 m (reference); 100 m (undersized)

Run the example in BoreTherm

  1. Start with File → New from example.
  2. Press Calculate.
  3. Open Results → Mean fluid temperature for the monthly curve and Results → Annual minimum / maximum for the extremes of every year.
  4. Results → Results summary lists the resistances, the g-function, the pump power and the freezing check.
02 / How BoreTherm calculates it

What Calculate computes

1 Ground at mid-depthTm = Ts + q_geo (H/2) / λ= 10.73 °C2 Borehole resistancefluid, flow, pipes, grout→ Rb 0.115, Rb* 0.119 m·K/W3 g-function of the fieldfinite line sources,all boreholes interacting4 Superpositionmonthly steps + 6 h peaksTf = Tm + ΔT ground + q Rb*5 Ground loadsextraction 153 MWh/a,injection 54 MWh/a6 Extremes and checksannual min / max of baseand peaks; freezingTfMin −2.41 °C (year 25), TfMax 16.03 °C (year 1)
The steps of Calculate for the office field (16 × 150 m, 2,400 m).
  1. Ground at mid-depth9 °C at the surface plus 0.06 W/m² over 2.6 W/(m·K) over half the borehole length (75 m): Tm = 10.73 °C.
  2. Borehole resistanceFrom the single U, the grout and the glycol flow: Rb* = 0.119 m·K/W.
  3. g-functionThe response of the 4 × 4 field to a constant load per metre, from minutes to 25 years.
  4. Ground loads153 MWh extracted and 54 MWh injected a year; peaks up to 74 kW (30.7 W/m).
  5. SuperpositionEach month's load change is a step on the g-function; the peak is superposed at the end of the month. Tf = Tm + ground temperature change + q Rb*.
  6. Extremes and checksThe coldest month is a January in year 25: the net extraction cools the field every year. The warmest is a July in year 1.
03 / In BoreTherm

The example in BoreTherm

Results → Mean fluid temperature: base load and peaks, 25 years.
Results → Mean fluid temperature: base load and peaks, 25 years.
Results → Annual minimum / maximum.
Results → Annual minimum / maximum.
Results → Results summary: field, resistances, temperatures, checks.
Results → Results summary: field, resistances, temperatures, checks.
04 / Results

Calculated results

Calculated with BoreTherm for every variant of the example. Displayed values are rounded.

Thermal simulation results plotted from BoreTherm output
Chart of the BoreTherm results in the tables of this section.

Temperatures by variant

VariantBoreholesLength H [m]Tf min [°C]Tf max [°C]Rb* [m K/W]Pump [W]Design limits
150 m (reference)16150.000-2.41316.0260.11943,033.2within limits
100 m16100.000-8.67218.0340.11702,022.1limits exceeded
05 / Discussion

What the example shows

The monthly result consists of month-end base temperatures plus the peak pulses. The minimum falls from year to year because the building takes more heat from the ground than it returns in summer. The decline slows down: 0.9 K in the first year, 0.05 K in the last.

The 100 m variant keeps the limits and the loads: BoreTherm reports −8.67 °C and marks the limits as exceeded. The next example finds the length that just meets them.