What the example does
On a 40 m × 30 m plot, BoreTherm searches for the best field for the office building: line, L-shape, U-shape, open rectangle and rectangle, 4 to 40 boreholes, spacing 5 to 12 m, depth 60 to 250 m. Three objectives are compared: the shortest total length, the lowest installation cost and the lowest life-cycle cost.
Inputs
| Input | Value |
|---|---|
| Field | 16 boreholes, 4 × 4 rectangle, spacing 6.0 × 6.0 m |
| Boreholes | length 150.0 m, top 4.0 m below the surface, diameter 140 mm |
| Construction | single U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K) |
| Ground | thermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m² |
| Fluid and flow | 25 % monopropylene glycol, 0.50 l/s per borehole |
| Loads | monthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h |
| Heat pump | seasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling |
| Design limits | mean fluid temperature between −3.0 °C and 20.0 °C |
| Period | 25 years |
| Plot | 40 m × 30 m |
| Search | 5 layout types, 4–40 boreholes, spacing 5–12 m, depth 60–250 m |
| Costs | 5,000 EUR fixed, 800 EUR per borehole, 45 EUR/m drilling, 60 EUR/m trench |
Run the example in BoreTherm
- Press Optimize. In the dialog, set the plot, the layout types, the ranges and the objective.
- Run the search. Results → Optimization candidates lists the best layouts, best first, with their plan.
- Select a candidate and apply it to the project, then calculate it again.
How Optimize searches the plot
- CandidatesBoreTherm generates all layouts of the selected types that fit on the plot.
- Size eachEach candidate gets the length that just meets the limits.
- Feasible?Candidates outside the depth range are dropped.
- CostThe cost model adds the fixed cost, the boreholes, the drilled metres and the trench.
- RankTotal length and installation cost lead to the same field here. The life-cycle cost adds the energy of the heat pump over the years and prefers a longer field (180.5 m) with warmer fluid and a better efficiency.
- Keep the bestThe candidates are proposals; none is applied automatically.
The example in BoreTherm
Calculated results
Calculated with BoreTherm for every variant of the example. Displayed values are rounded.
| Objective | Retained | Layout | Count | Spacing [m] | H [m] | Total [m] | Install net [EUR] | LCOH [EUR/kWh] |
|---|---|---|---|---|---|---|---|---|
| TotalLength | 9 | Rectangle | 12 | 8.000 | 164.013 | 1,968.157 | 108,447.05 | — |
| TotalCost | 9 | Rectangle | 12 | 8.000 | 164.013 | 1,968.157 | 108,447.05 | — |
| LifeCycleCost | 9 | Rectangle | 12 | 8.000 | 180.528 | 2,166.338 | 117,365.21 | 0.1476 |
Temperatures by variant
| Variant | Boreholes | Length H [m] | Tf min [°C] | Tf max [°C] | Rb* [m K/W] | Pump [W] | Design limits |
|---|---|---|---|---|---|---|---|
| input design | 16 | 150.000 | -2.413 | 16.026 | 0.1194 | 3,033.2 | within limits |
| best by life-cycle cost | 16 | 150.000 | -2.413 | 16.026 | 0.1194 | 3,033.2 | within limits |
| best by cost | 16 | 150.000 | -2.413 | 16.026 | 0.1194 | 3,033.2 | within limits |
| best by length | 16 | 150.000 | -2.413 | 16.026 | 0.1194 | 3,033.2 | within limits |
What the example shows
Under these assumptions a 12-borehole rectangle at 8 m spacing is best by length and by installation cost (1,968 m, about 108,000 EUR). The life-cycle objective chooses longer boreholes, because a warmer source saves heat pump electricity over 20 years.
The feasible set is limited by the plot, the counts, the spacing and the depth range. Cost figures are estimates from the project's unit rates; the life-cycle objective uses the heating-system comparison data of the project.