BoreTherm / Example libraryExample 10 / 23
Worked feature example

Hydraulic networks

Compare the parallel office field with pairs in series and an explicitly connected unequal-string network. Inspect flow sharing, string pressure losses and pumping power.

16Boreholes
-2.41 °CMinimum mean fluid temperature
16.03 °CMaximum mean fluid temperature
3Variants compared
01 / Project

What the example does

The 16 boreholes of the office field are connected in three ways: all in parallel (the reference), in pairs in series, and as explicitly connected strings of unequal length. The total flow is the same. The example shows how the connection changes the flow per borehole, the resistance and the pump pressure.

Inputs

InputValue
Field16 boreholes, 4 × 4 rectangle, spacing 6.0 × 6.0 m
Boreholeslength 150.0 m, top 4.0 m below the surface, diameter 140 mm
Constructionsingle U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K)
Groundthermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m²
Fluid and flow25 % monopropylene glycol, 0.50 l/s per borehole
Loadsmonthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h
Heat pumpseasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling
Design limitsmean fluid temperature between −3.0 °C and 20.0 °C
Period25 years
Variants16 in parallel; 8 strings of 2 in series; connected strings of unequal length

Run the example in BoreTherm

  1. Open Design → Field layout and switch the edit mode to Connect. Draw strings from the header through the boreholes.
  2. On Design → Fluid & flow the network shows the flow and pressure drop of every string.
  3. Press Calculate; Results → Results summary lists the network.
02 / How BoreTherm calculates it

Flow distribution in the network

1 Stringsboreholes in series per string,strings in parallel2 Flow splitequal pressure drop acrossall strings → flow per string3 Per boreholemore flow in short strings,less in long ones4 ResistanceRb* from the flow of eachborehole5 Field responseborehole temperaturesweighted by the flows6 Pumppressure of the worst string× total flow / efficiencyPairs in series: pump 20.1 kW instead of 3.0 kW
Series connections double the flow per borehole and the pressure drop per string.
  1. StringsEach string is a chain of boreholes; the strings are connected in parallel to the header.
  2. Flow splitAll strings see the same pressure difference, so a long string gets less flow.
  3. Per boreholeIn pairs, each borehole carries the flow of a string: twice the parallel flow.
  4. ResistanceMore flow per pipe gives turbulent flow and a lower Rb* (0.114 instead of 0.119).
  5. Field responseThe outlet of one borehole is the inlet of the next.
  6. PumpThe pressure drop grows with the square of the velocity and the length of the string.
03 / In BoreTherm

The example in BoreTherm

Connect mode on the Field layout page: the strings drawn on the plan.
Connect mode on the Field layout page: the strings drawn on the plan.
Design → Fluid & flow: flow and pressure drop per string.
Design → Fluid & flow: flow and pressure drop per string.
Results → Results summary with the network.
Results → Results summary with the network.
04 / Results

Calculated results

Calculated with BoreTherm for every variant of the example. Displayed values are rounded.

Hydraulic networks results plotted from BoreTherm output
Chart of the BoreTherm results in the tables of this section.

Temperatures by variant

VariantBoreholesLength H [m]Tf min [°C]Tf max [°C]Rb* [m K/W]Pump [W]Design limits
all in parallel16150.000-2.41316.0260.11943,033.2within limits
pairs in series16150.000-2.23715.8970.113720,060.1within limits
strings of unequal length16150.000-2.20715.8760.112743,033.1within limits
05 / Discussion

What the example shows

The series connections improve the minimum temperature only slightly (by 0.2 K) but need much more pump power: 20 kW for pairs and 43 kW for the longest strings, against 3 kW in parallel. Check the flow and resistance of every string, not only the field-average temperature.