What the example does
An office on an L-shaped plot: a drawing gives the drilling boundary, the building, trees, a sewer corridor and the connection point. BoreTherm checks the existing 16-borehole field against the setbacks and fills the usable area with four patterns.
Inputs
| Input | Value |
|---|---|
| Field | 16 boreholes, free positions |
| Boreholes | length 150.0 m, top 4.0 m below the surface, diameter 140 mm |
| Construction | single U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K) |
| Ground | thermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m² |
| Fluid and flow | 25 % monopropylene glycol, 0.50 l/s per borehole |
| Loads | monthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h |
| Heat pump | seasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling |
| Design limits | mean fluid temperature between −3.0 °C and 20.0 °C |
| Period | 25 years |
| Site | plot from a DXF drawing, building, trees, sewer corridor, connection point; setbacks from each object |
Run the example in BoreTherm
- Open Design → Field layout and switch the view to Site. Import the drawing and assign its layers: plot, building, obstacles, connection point.
- Set the setbacks; the usable drilling area is shaded.
- Check site lists every violation of a setback; Fill area places a pattern in the usable area.
- Press Calculate for the field on the plot.
From the drawing to a field
- DrawingThe layers of the DXF drawing become site objects.
- SetbacksEach object gets a distance it must keep from boreholes.
- Usable areaWhat remains of the plot is the drilling area.
- FillThe pattern generator places positions at the minimum spacing inside the area.
- SelectionThe positions closest to the connection point are taken first.
- TrenchThe trench length is estimated from the heads to the connection point.
The example in BoreTherm
Calculated results
Calculated with BoreTherm for every variant of the example. Displayed values are rounded.
| Site-check quantity | Value |
|---|---|
| Valid field | Yes |
| Drilling area [m²] | 1,168.164 |
| Trench [m] | 110.460 |
| Violations | 0 |
| Fill pattern | Capacity [positions] | Selected heads | Trench [m] |
|---|---|---|---|
| grid | 28 | 16 | 110.460 |
| staggered | 32 | 16 | 124.339 |
| rowwise | 30 | 16 | 116.647 |
| perimeter | 22 | 16 | 124.700 |
Temperatures by variant
| Variant | Boreholes | Length H [m] | Tf min [°C] | Tf max [°C] | Rb* [m K/W] | Pump [W] | Design limits |
|---|---|---|---|---|---|---|---|
| existing field | 16 | 150.000 | -1.130 | 16.416 | 0.1194 | 3,033.2 | within limits |
| grid fill | 16 | 150.000 | -1.130 | 16.416 | 0.1194 | 3,033.2 | within limits |
| perimeter fill | 16 | 150.000 | -0.551 | 16.475 | 0.1194 | 3,033.2 | within limits |
| row-wise fill | 16 | 150.000 | -1.112 | 16.434 | 0.1194 | 3,033.2 | within limits |
| staggered fill | 16 | 150.000 | -0.975 | 16.423 | 0.1194 | 3,033.2 | within limits |
What the example shows
All four fills keep 16 boreholes and the 150 m length, so their temperatures differ only by the arrangement: the perimeter pattern spreads the boreholes along the edge and is the warmest. The grid pattern needs the shortest trench.
The setbacks are input assumptions. A site check does not establish a drilling permit or environmental compliance.