What the example does
How much longer must the office boreholes be if the ground conducts less heat, or the building needs more? A parametric study runs the sizing for a grid of nine combinations: ground conductivity 2.0, 2.6 and 3.2 W/(m·K) times heating demand 0.8, 1.0 and 1.2 of the reference.
Inputs
| Input | Value |
|---|---|
| Field | 16 boreholes, 4 × 4 rectangle, spacing 6.0 × 6.0 m |
| Boreholes | length 150.0 m, top 4.0 m below the surface, diameter 140 mm |
| Construction | single U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K) |
| Ground | thermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m² |
| Fluid and flow | 25 % monopropylene glycol, 0.50 l/s per borehole |
| Loads | monthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h |
| Heat pump | seasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling |
| Design limits | mean fluid temperature between −3.0 °C and 20.0 °C |
| Period | 25 years |
| Study | grid: ground conductivity 2.0 / 2.6 / 3.2 W/(m·K) × heating demand 0.8 / 1.0 / 1.2; each run sized |
Run the example in BoreTherm
- Press Parametric study. Choose the parameters, their values and the kind of study (one at a time, or a full grid), and whether each run is simulated or sized.
- Run the study.
- Advanced analysis → Studies & uncertainty → Parametric study shows the lines, the heat map, the tornado chart and the table of all runs.
- A run can be applied to the project from the table.
How a study runs
- AxesEach parameter is varied over the listed values, in display units.
- RunsThe grid combines every value of one axis with every value of the other.
- Size eachEvery run finds its own required length.
- CollectThe results are kept per run, with the values that produced them.
- ChartsLines and the heat map show the grid; a one-at-a-time study gives the tornado chart.
The example in BoreTherm
Calculated results
Calculated with BoreTherm for every variant of the example. Displayed values are rounded.
| λ [W/(m K)] | Heating multiplier | H [m] | Total [m] | Tf min [°C] |
|---|---|---|---|---|
| 2.000 | 0.800 | 136.851 | 2,189.622 | -2.993 |
| 2.000 | 1.000 | 160.539 | 2,568.619 | -2.995 |
| 2.000 | 1.200 | 183.761 | 2,940.183 | -2.999 |
| 2.600 | 0.800 | 123.001 | 1,968.010 | -2.998 |
| 2.600 | 1.000 | 143.718 | 2,299.484 | -2.998 |
| 2.600 | 1.200 | 164.418 | 2,630.694 | -2.998 |
| 3.200 | 0.800 | 112.435 | 1,798.960 | -2.998 |
| 3.200 | 1.000 | 130.594 | 2,089.496 | -2.998 |
| 3.200 | 1.200 | 148.998 | 2,383.975 | -2.998 |
Temperatures by variant
| Variant | Boreholes | Length H [m] | Tf min [°C] | Tf max [°C] | Rb* [m K/W] | Pump [W] | Design limits |
|---|---|---|---|---|---|---|---|
| office reference | 16 | 150.000 | -2.413 | 16.026 | 0.1194 | 3,033.2 | within limits |
What the example shows
At the reference demand the length falls from 161 m to 131 m as the conductivity rises from 2.0 to 3.2 W/(m·K). A 20 % change in heating demand changes the length by about 14 %. Cooling, hot water, geometry and limits stay at their saved values in every run.
The grid is a deterministic sensitivity study: it says how the result responds, not how likely each value is. For that, see the Monte Carlo example.