What the example does
One 40 m borehole in an aquifer with groundwater flow feeds a heat pump. The 2D design method, the 3D finite-element model of the ground and the fully coupled heat and groundwater model are compared, and the borehole is sized in 2D and in 3D.
Inputs
| Input | Value |
|---|---|
| Field | 1 borehole, free positions |
| Boreholes | length 40.0 m, top 4.0 m below the surface, diameter 110 mm |
| Construction | single U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K) |
| Ground | thermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m² |
| Fluid and flow | 25 % monopropylene glycol, 0.50 l/s per borehole |
| Loads | monthly: heating 13 MWh, hot water 0 MWh and cooling 0 MWh per year; peaks 0 kW heating and 0 kW cooling |
| Design limits | mean fluid temperature between 2.0 °C and 30.0 °C |
| Period | 1 year |
| Models | 2D analytic; 3D analysis (FEM, conduction); full FEM with coupled heat and groundwater flow; transient boreholes with a pump stop |
Run the example in BoreTherm
- Open Advanced analysis → 3D / Full FEM → Full FEM → Physics & run. Choose the physics (conduction, groundwater flow, coupled), the mesh and the time step.
- Check Full FEM → Materials and Full FEM → Groundwater flow: the hydraulic properties of the layers and the boundary heads.
- Run the full 3D simulation, then compare on Results → Full FEM results and 3D / Full FEM → 3D analysis. Calculate still gives the 2D design result.
From the 2D design to the coupled 3D model
- MeshThe ground around the borehole is meshed in 3D, refined near the borehole.
- GroundwaterThe groundwater flow is solved first from the hydraulic heads and the permeability of the layers. The water balance closes to machine precision.
- Heat transportHeat is conducted through the ground and carried with the water.
- Borehole couplingThe borehole's fluid, pipes and grout exchange heat with the mesh at the borehole wall.
- Fluid temperatureThe coupled model gives −5.13 °C, close to the 2D result (−5.25 °C).
- SizingBoth models need about 76 m for the 2 °C limit.
The example in BoreTherm
Calculated results
Calculated with BoreTherm for every variant of the example. Displayed values are rounded.
| Model / project | Tf min [°C] | Tf max [°C] | Limits met |
|---|---|---|---|
| 2D analytic, aquifer case | -5.247 | -2.690 | No |
| Full FEM coupled TH | -5.131 | -2.747 | No |
| Full FEM transient pump stop | 0.034 | 9.998 | Yes |
| Basic FEM | -2.909 | 8.605 | Yes |
| Groundwater / sizing metric | Value |
|---|---|
| Mean Darcy speed [m/s] | 0.0000000990 |
| Relative water-balance residual | 2.719688351451516e-15 |
| Mesh nodes | 13230 |
| Mesh elements | 11600 |
| Required H, 2D [m] | 75.950 |
| Required H, full 3D [m] | 75.134 |
Temperatures by variant
| Variant | Boreholes | Length H [m] | Tf min [°C] | Tf max [°C] | Rb* [m K/W] | Pump [W] | Design limits |
|---|---|---|---|---|---|---|---|
| 3D analysis, 100 m | 1 | 100.000 | -2.909 | 8.605 | 0.1425 | 62.8 | within limits |
| 2D, aquifer borehole | 1 | 40.000 | -5.247 | -2.690 | 0.0900 | 50.6 | limits exceeded |
| full FEM, coupled | 1 | 40.000 | -5.131 | -2.747 | 0.0900 | 50.6 | limits exceeded |
| 3D sizing check, 100 m | 1 | 100.000 | -2.933 | 8.601 | 0.1425 | 62.8 | within limits |
| transient boreholes | 1 | 50.000 | 0.034 | 9.998 | 0.1092 | 34.5 | within limits |
| transient, pump stop | 1 | 50.000 | 0.036 | 9.998 | 0.1092 | 34.5 | within limits |
What the example shows
The 40 m borehole fails its 2 °C minimum in both models; sizing asks for 75.95 m in 2D and 75.13 m with the full 3D model. For this case the 2D method with groundwater is close to the coupled model.
The mesh is coarse for a short run time, and the hydraulic properties are assumptions. Check the solver, energy balance and mesh messages of every run before using its result.