What the example does
How far does the cooled ground around the office field reach after 25 years, and does it cross the plot boundary? BoreTherm maps the temperature change on the site plan, measures the −3 K and +3 K regions and their clearances to the plot, and repeats it with groundwater flow.
Inputs
| Input | Value |
|---|---|
| Field | 16 boreholes, free positions |
| Boreholes | length 150.0 m, top 4.0 m below the surface, diameter 140 mm |
| Construction | single U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K) |
| Ground | thermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m² |
| Fluid and flow | 25 % monopropylene glycol, 0.50 l/s per borehole |
| Loads | monthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h |
| Heat pump | seasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling |
| Design limits | mean fluid temperature between −3.0 °C and 20.0 °C |
| Period | 25 years |
| Plume | thresholds −3 K and +3 K at the end of the design period; plot boundary as evaluation object |
| Variants | no groundwater; groundwater flow |
Run the example in BoreTherm
- Press Calculate, then open Results → Thermal plume.
- Choose the depth, the time and the thresholds; the map shows the temperature change on the site plan.
- The tabs Extents and Clearances list the area, the reach and the distance of every threshold region to the site objects.
How the plume is calculated
- Base loadsShort peaks do not reach far into the ground and are left out.
- Point responseEach map point gets the temperature change caused by every borehole.
- SuperpositionThe load history is superposed as in the design calculation.
- ThresholdsThe regions colder than −3 K (or warmer than +3 K) are traced on the map.
- ClearancesA negative clearance means that the region crosses the object.
The example in BoreTherm
Calculated results
Calculated with BoreTherm for every variant of the example. Displayed values are rounded.
| Variant | Threshold [K] | Area [m²] | Reach [m] | Downstream [m] | Clearance |
|---|---|---|---|---|---|
| no groundwater | -3.000 | 1,550.674 | 9.928 | — | PLOT: -8.428 m |
| no groundwater | 3.000 | 0.000 | 0.000 | — | PLOT: — m |
| groundwater flow | -3.000 | 64.221 | 2.277 | 2.228 | PLOT: 0.747 m |
| groundwater flow | 3.000 | 0.000 | 0.000 | — | PLOT: — m |
Temperatures by variant
| Variant | Boreholes | Length H [m] | Tf min [°C] | Tf max [°C] | Rb* [m K/W] | Pump [W] | Design limits |
|---|---|---|---|---|---|---|---|
| no groundwater | 16 | 150.000 | -1.130 | 16.416 | 0.1194 | 3,033.2 | within limits |
| groundwater flow | 16 | 150.000 | 0.419 | 16.423 | 0.1194 | 3,033.2 | within limits |
What the example shows
Without groundwater the −3 K region covers 1,551 m² and crosses the plot boundary by 8.4 m. With groundwater it shrinks to 64 m² and stays inside the plot, but it is carried 2.2 m downstream. The +3 K threshold is never reached: the building extracts more heat than it returns.
A threshold crossing is a calculated result under the stated loads and ground. Whether it matters is a question for the permit authority.