What the example does
A borehole thermal energy store: 37 boreholes of 50 m on a compact hexagonal grid, charged with solar or waste heat in summer and discharged in winter, for three years. The flow reverses between charging and discharging. BoreTherm calculates the energy charged, discharged and recovered every year.
Inputs
| Input | Value |
|---|---|
| Field | 37 boreholes, hexagonal grid, spacing 3.0 m |
| Boreholes | length 50.0 m, top 1.0 m below the surface, diameter 150 mm |
| Construction | single U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.50 W/(m·K) |
| Ground | thermal conductivity 2.00 W/(m·K), heat capacity 2.40 MJ/(m³·K), surface temperature 10.0 °C, geothermal heat flux 0.000 W/m² |
| Fluid and flow | water, 2.92 l/s for the whole field |
| Loads | a fluid-side time series: inlet temperature, flow and flow direction, hour by hour |
| Design limits | mean fluid temperature between 2.0 °C and 80.0 °C |
| Period | 3 years |
| Operation | charging May to September at 70 °C inlet, entering at the centre; discharging November to March at 30 °C inlet, entering at the outer ring; 0.25 kg/s per borehole; six strings, each ring by ring |
Run the example in BoreTherm
- Open Design → Loads: the fluid-side time series (inlet temperature, flow and direction).
- On Design → Design limits & simulation the borehole model is Dynamic, with the storage connected ring-wise.
- Press Calculate and open Results → Storage for the yearly energies and Results → Dynamic model for the temperatures.
How the storage is calculated
- Time seriesThe store is driven by the fluid: inlet temperature, flow and its direction.
- StringsSix strings run ring by ring from the centre outwards. Charging enters at the centre, so the centre becomes the hottest part; discharging reverses the flow and enters at the cool outer ring.
- BoreholesA steady borehole model runs the three years hour by hour. For two weeks around the first discharge of year 3, the dynamic model follows the fluid through the pipes, with its transit time and the heat stored in the grout.
- GroundThe ground response of every borehole includes the heat of the earlier months.
- EnergiesThe heat exchanged is integrated hour by hour, for charging and discharging.
- RecoveryRecovery is the discharged energy divided by the charged energy of the same year.
The example in BoreTherm
Calculated results
Calculated with BoreTherm for every variant of the example. Displayed values are rounded.
| Year | Charged [MWh] | Discharged [MWh] | Recovery [%] | Charging [h] | Discharging [h] |
|---|---|---|---|---|---|
| 1 | 580.050 | 92.234 | 15.9 | 3,889.000 | 3,407.000 |
| 2 | 425.506 | 138.165 | 32.5 | 3,672.000 | 3,624.000 |
| 3 | 401.040 | 152.037 | 37.9 | 3,672.000 | 3,624.000 |
Temperatures by variant
| Variant | Boreholes | Length H [m] | Tf min [°C] | Tf max [°C] | Rb* [m K/W] | Pump [W] | Design limits |
|---|---|---|---|---|---|---|---|
| hexagonal store, 37 × 50 m | 37 | 50.000 | 10.000 | 67.115 | 0.1279 | 497.9 | within limits |
What the example shows
The recovery grows from 15.9 % in the first year to 37.9 % in the third: the ground around the store warms up, and less of the charged heat is lost to heating it. A store reaches a steady recovery only after several years.
Recovery depends on the operating period it is computed for. For the storage model, the theory manual describes the comparison with an independent 3D model, including the cases where the discharged energy differs by more than 3 %.