Heat pump setup
The one place for the project's heat pump, which converts the building loads into ground loads and so changes the borefield calculation. How should heat-pump performance be calculated: Fixed seasonal efficiency (the seasonal performance factors (SPF) of heating, domestic hot water and active cooling convert the loads) or Temperature-dependent performance (the heat pump model gives the coefficient of performance (COP) at every operating point, calculated together with the fluid temperatures, so the seasonal performance factor is a result). In the temperature-dependent mode the seasonal performance factors are the starting values of the first pass. Cooling: passive (free) cooling sends the cooling energy to the ground unchanged; otherwise the cooling is active, by the heat pump itself or, with Active cooling by the heat pump cleared, by a separate unit (this tick is used by the equipment check only and does not change the ground loads). Heat pump model: a summary of the coefficient of performance (COP) model and heating curve, and Edit heat pump model to change them; it is used for the borefield calculation in the temperature-dependent mode, for the design point of the equipment requirement sheet and for the ground-source variant of the comparison; the summary names the candidate of Equipment selection it came from. With ground loads (direct input or time series) the conversion does not apply: the settings are kept and disabled. Every edit is one undo step; switching the mode keeps all values and marks the results out of date. Loads and Comparison show a summary and link here.
Step-by-step workflows · Menus and keyboard

| Control | Meaning / action | Unit | Range / choices | Example value |
|---|---|---|---|---|
| Fixed seasonal efficiency | Selects this alternative. | |||
| Temperature-dependent performance | Selects this alternative. | |||
| Heating: | Seasonal performance factor (SPF) in heating. Ground extraction = Q_heat · (SPF − 1) / SPF. | 1 to 50 | 3.8 | |
| Domestic hot water: | Seasonal performance factor (SPF) for domestic hot water. Ground extraction = Q_dhw · (SPF − 1) / SPF. | 1 to 50 | 2.8 | |
| Active cooling: | Seasonal performance factor (SPF) of active cooling. Ground injection = Q_cool · (SPF + 1) / SPF. Not used with passive cooling. | 1 to 50 | 5 | |
| Passive (free) cooling | Free cooling without a heat pump: the cooling energy goes to the ground unchanged (ground injection = Q_cool). | |||
| Active cooling by the heat pump | On: the heat pump also cools actively (reversible), so the equipment check tests its cooling capacity and cooling efficiency (EER). Off: a separate unit cools; the requirement sheet shows its cooling lines, which are not checked against the candidates. Used by the equipment selection only; it does not change the ground loads. | |||
| Edit heat pump model… | The coefficient of performance (COP) model, the heating curve and the operating settings of the project's heat pump. Specialist options: Edit as JSON in the dialog. |