BoreTherm Online help

Heat pump setup

The one place for the project's heat pump, which converts the building loads into ground loads and so changes the borefield calculation. How should heat-pump performance be calculated: Fixed seasonal efficiency (the seasonal performance factors (SPF) of heating, domestic hot water and active cooling convert the loads) or Temperature-dependent performance (the heat pump model gives the coefficient of performance (COP) at every operating point, calculated together with the fluid temperatures, so the seasonal performance factor is a result). In the temperature-dependent mode the seasonal performance factors are the starting values of the first pass. Cooling: passive (free) cooling sends the cooling energy to the ground unchanged; otherwise the cooling is active, by the heat pump itself or, with Active cooling by the heat pump cleared, by a separate unit (this tick is used by the equipment check only and does not change the ground loads). Heat pump model: a summary of the coefficient of performance (COP) model and heating curve, and Edit heat pump model to change them; it is used for the borefield calculation in the temperature-dependent mode, for the design point of the equipment requirement sheet and for the ground-source variant of the comparison; the summary names the candidate of Equipment selection it came from. With ground loads (direct input or time series) the conversion does not apply: the settings are kept and disabled. Every edit is one undo step; switching the mode keeps all values and marks the results out of date. Loads and Comparison show a summary and link here.

Step-by-step workflows · Menus and keyboard

Heat pump setup in BoreTherm
English GUI; click to enlarge.
Controls captured from the BoreTherm GUI. Ranges are interface bounds; example values depend on the open project.
ControlMeaning / actionUnitRange / choicesExample value
Fixed seasonal efficiencySelects this alternative.
Temperature-dependent performanceSelects this alternative.
Heating:Seasonal performance factor (SPF) in heating. Ground extraction = Q_heat · (SPF − 1) / SPF.1 to 503.8
Domestic hot water:Seasonal performance factor (SPF) for domestic hot water. Ground extraction = Q_dhw · (SPF − 1) / SPF.1 to 502.8
Active cooling:Seasonal performance factor (SPF) of active cooling. Ground injection = Q_cool · (SPF + 1) / SPF. Not used with passive cooling.1 to 505
Passive (free) coolingFree cooling without a heat pump: the cooling energy goes to the ground unchanged (ground injection = Q_cool).
Active cooling by the heat pumpOn: the heat pump also cools actively (reversible), so the equipment check tests its cooling capacity and cooling efficiency (EER). Off: a separate unit cools; the requirement sheet shows its cooling lines, which are not checked against the candidates. Used by the equipment selection only; it does not change the ground loads.
Edit heat pump model…The coefficient of performance (COP) model, the heating curve and the operating settings of the project's heat pump. Specialist options: Edit as JSON in the dialog.