Time series import
Map source columns, time units, temperature/power/flow units and sign conventions. Inspect the preview, timestamp coverage and interpolation before applying. Short coverage or invalid timestamps must be addressed before design use.
Step-by-step workflows · Menus and keyboard

| Control | Meaning / action | Unit | Range / choices | Example value |
|---|---|---|---|---|
| Time series file | Local file/folder selected in this example. | |||
| Browse… | Choose a local file or folder. | |||
| Time: | Unit of the time column (time since the start of operation; only the step matters). | seconds / minutes / hours / days | ||
| Ignore the time column, rows every | For files whose time column is a row number or a date: the rows follow each other at this constant step. | |||
| Step between two rows. | Step between two rows. | min | 0.1 to 1440 | 60 |
| Ground load: | Select one of the listed alternatives. | W / kW | ||
| Sign: | Sign convention of the load column. BoreTherm stores ground loads with > 0 = injection. | > 0: heat injected into the ground (cooling) / > 0: heat extracted from the ground (heating) | ||
| Flow: | Unit of the flow column (0 = pump off). A mass flow is stored as it is and converted to a volume flow with the density of the fluid at the inlet temperature of each step. | m³/s / l/s / m³/h / l/min / kg/s (mass flow) / kg/h (mass flow) / t/h (mass flow) | ||
| Flow refers to: | Whole field: the flow of the pump. Per borehole: the mean flow through one borehole; the field's flow follows from the borehole connections (boreholes in series carry the same flow one after the other). | Whole field / Per borehole | ||
| Direction column: | Optional column with the flow direction: +1 normal (the connections as drawn: charging), −1 reversed (discharging), 0 keep the previous direction. | Automatic (a column named "direction") / None / Column 1 / Column 2 / Column 3 | ||
| Use the dynamic borehole model with this series (flow, direction and inlet temperature from the file) | Switches the borehole model to Dynamic (Design limits simulation) and lets it take the inlet temperature, the flow and the flow direction from the columns of the series. The steady and short-time models use the hour means of the load and the project's nominal flow. | |||
| Import | Import the mapped time series after checking units, signs and coverage. | |||
| Cancel | Close without accepting unapplied edits. |