The classic monthly method knows one hydraulic parameter besides the flow: the series factor , with the flow per borehole ((5.25)). BoreTherm describes the connections explicitly as a network: a set of parallel strings, each an ordered chain of boreholes (the outlet of borehole k is the inlet of borehole k + 1), all between the supply and the return header and all starting at the same inlet temperature. A borehole in no string is a string of its own, so the empty network is “all in parallel”, and without explicit strings generates strings of consecutive boreholes. A network is valid when every borehole appears at most once (no loop, no branch), no string is empty and no index lies outside the field.
14.1 Hydraulics
The pressure drop of string at the flow is the sum of its borehole loops ((5.24), U-tubes split equally, coaxial annulus plus inner pipe) and a minor loss of its connection to the headers:
with the mean velocity in one borehole pipe and the minor-loss coefficient (tees, valves, bends; the header pipes themselves are not modelled). Two flow splits:
- Equal flow (balancing valves; the classic assumption): every string gets (or the given flow per string); the pump overcomes the largest string drop, , and the others are throttled.
- Equal pressure drop (ideal or reverse-return (Tichelmann) headers, no valves): find with
where inverts the increasing . Strings of the same total length are one class; both levels are solved by the Illinois false-position method with a bisection safeguard (the friction factor jumps at Re = 2300, so is increasing but not continuous), and the class flows are finally scaled so that the total is conserved to rounding. Shorter strings take more flow. The pump power is ; the default network keeps the classic formulas (5.25) bit for bit.
14.2 Resistances and fluid temperatures
is a property of one U-tube at its own flow and length: a “string at ” would be wrong and is not used. Every borehole gets at the flow of its string, its own and H (with sections), and the simulation combines them with (13.6) over the distinct , so the temporal superposition is unchanged and uses one field value. The design criterion stays the field mean fluid temperature. With the heat rate spread uniformly over the length, , the outlet of string and the mean temperature of its borehole are
The results give them at the month and load case (base, heating peak, cooling peak) of and , or at the hour of the extreme. They are read-outs: the g-function still assumes one uniform wall temperature, not the axial fluid profile of each string. Example (office 4 × 4, rows of four in series, 0.5 l/s per string): at = −2.41 °C (January of year 25, heating peak) the strings enter at −7.05 °C and leave at 2.22 °C; the first borehole of each string averages −5.89 °C, the last 1.06 °C.
| Case (office 4 × 4, 16 × 150 m) | Total flow [l/s] | [m K/W] | Pump ΔP [kPa] | Pump [W] | [°C] | Sized H [m] |
|---|---|---|---|---|---|---|
| All parallel, 0.5 l/s per borehole (the example) | 8.0 | 0.1194 | 189.6 | 3033 | −2.413 | 143.72 |
| Strings of 2, 0.5 l/s per string | 4.0 | 0.1194 | 379.1 | 3033 | −2.413 | 143.72 |
| Rows of 4, 0.5 l/s per string | 2.0 | 0.1194 | 758.3 | 3033 | −2.413 | 143.72 |
| Rows of 4, 8 l/s in total (= series factor 4) | 8.0 | 0.1117 | 8421 | 134 741 | −2.176 | 141.31 |
| Mixed 120/180 m, all parallel, equal flow | 8.0 | 0.1199 | 227.5 | 3640 | −1.869 | 138.02 |
| Mixed 120/180 m, equal pressure drop | 8.0 | 0.1209 | 183.6 | 2937 | −1.898 | 138.30 |
| Mixed 120/180 m, equal pressure drop, K = 10 | 8.0 | 0.1208 | 188.2 | 3011 | −1.897 | 138.29 |
At the same flow per borehole, strings in series change nothing in the mean-temperature model of the classic method ( is that of one borehole at its flow and the pump power is the same product ): the difference is in the string temperatures and in the flow the heat pump sees. The series-factor row and the explicit rows of four agree to . Equal pressure drop gives the shorter boreholes more flow; the field rises slightly and drops by 0.03 K, while the pump needs less power because no string is throttled.
Editor and the classic method. The connection editor (arrows from borehole to borehole: click-to-connect, drawn paths, generators all-parallel, rows, columns, serpentine, nearest neighbour, Tichelmann = all parallel with equal pressure drop) refuses branches and loops while editing. The classic monthly method can represent a network only when all strings have the same length and the split is equal flow without minor losses; anything else is reported as outside the classic method.