13. Inclined boreholes and fields of unequal boreholes

Boreholes may be inclined up to 85° from the vertical, and a custom field may mix lengths, depths and radii. The g-function keeps its definition (UBWT, UHTR or UFT; ts=H¯2/(9α) with the mean length along the axis); only the segment-to-segment response (4.4) changes.

13.1 Geometry

In a frame with z = depth, positive downwards, a borehole has its head at (x,y,D), tilt θ from the vertical and azimuth φ from +x towards +y:

𝐞=(sinθcosφ,sinθsinφ,cosθ),𝐩(u)=𝐩0+u𝐞,0≤u≤H
(13.1)

The active length H is measured along the axis and D stays the vertical depth of the head. A point u has the measured depth D+u (the coordinate of the borehole sections) and the vertical depth D+ucosθ. A negative tilt is the same borehole as |θ| at azimuth φ+π; tilt 0 takes exactly the vertical computation (bit-identical results). |θ|≤85°; in a field with an inclined borehole the heads must be at least rb,i+rb,j apart; the approximate FLS and groundwater flow are refused; the simulation warns when two axes come closer than 1 m.

13.2 Inclined finite line source

For an emitting segment 1 (start 𝐩1, axis 𝐞1, length H1) and a receiving segment 2 (𝐩2, 𝐞2, H2), integrating the continuous point source over both segments with the image of the emitter above the isothermal surface gives (Lazzarotto 2016)

h21(t)=F(t)2H2,F(t)=∫1/4αt∞G(s)sds,G(s)=J(s;1,2)−J(s;1′,2)
(13.2)
J(s)=∫0H1e−s2ρ2(u)[erf(s(H2−b(u)))+erf(sb(u))]du
(13.3)

where b(u)=(𝐩1+u𝐞1−𝐩2)·𝐞2 is the foot of the emitter point on the receiver's line and ρ2(u)=|𝐩1+u𝐞1−𝐩2−b(u)𝐞2|2 its squared distance from that line: b is linear and ρ2 quadratic in u, so the receiver integral is analytic and one integral over the emitter remains. 1′ is the image (z→−z). For vertical segments (13.2) is exactly (4.4)–(4.8), so inclined entries sit in the same response model and solvers; F is symmetric (H1h12=H2h21). The steady state is

F(∞)=∫0H1[A(u;1)−A(u;1′)]du,A=asinhH2−bρ+asinhbρ
(13.4)

13.3 Numerics

13.4 Self response and the wall convention

The wall temperature is taken at the borehole wall: every segment pair of one borehole puts the receiver line at rb from the axis, along the horizontal normal (−sinφ,cosφ,0). The real part is then the vertical self response (tilt-invariant, closed form) and the image part depends on the tilt; the model is continuous in θ and equals the vertical one at θ=0. An open-source g-function library uses the horizontal head distance max(dx2+dy2,rb2) for every pair, so for two different segments of one tilted borehole it puts the receiver on the axis. Its g-functions of tilted fields are therefore 0.12–0.18 % higher than BoreTherm's at 10–25°; with that one choice changed to the wall convention it agrees with BoreTherm to 7·10−11.

13.5 Response model, layers and the undisturbed temperature

The ground reference and Tm are those of the vertical extent:

Hv=1N∑iHicosθi,λref, αref, Tm over [D¯,D¯+Hv]
(13.5)

Sizing keeps the proportional length rule of Section 13.6 with Hv/H¯ fixed, and the optimizer enumerates vertical shapes only. The inclined ring layout places n heads on a circle of radius R0 at depth D, azimuth outwards, with R0≥1.1rb/sin(π/n). The classic monthly method has vertical boreholes only.

Figure 12 shows six 150 m boreholes whose heads share a 1.5 m circle. Vertical, they form a compact bundle whose g-function reaches 22.6 at ln(t/ts) = 3, more than a 3 × 2 field at 6 m spacing (16.1). Tilted outwards by 10°, 20° and 30° opposite feet lie 55, 106 and 153 m apart, and the steady g-function falls to 13.3, 11.0 and 9.7: the same length in the ground from one small drilling area interacts less than the vertical grid. Computing time (g-function at 50 times): 10 × 10 field 0.16 s vertical, 0.25 s tilted alike, 0.82 s tilted outwards (every pair its own class).

Ring of six boreholes (H = 150 m, D = 4 m, heads on a 1.5 m circle) tilted outwards: (a) section through two opposite boreholes; (b) g-functions, with a vertical 3 × 2 field at 6 m for comparison.
Figure 12. Ring of six boreholes (H = 150 m, D = 4 m, heads on a 1.5 m circle) tilted outwards: (a) section through two opposite boreholes; (b) g-functions, with a vertical 3 × 2 field at 6 m for comparison.

13.6 Fields of unequal boreholes

A custom layout may mix borehole lengths Hi and radii rb,i. Each distinct (rb,H) gets its own Rb,i* (Chapter 5; Rb* grows with H through the short-circuit term). The boreholes are in parallel between the common mean fluid temperature and the field-mean wall temperature, so borehole i takes Hi(Tf−Tb)/Rb,i* and the field value is the length-weighted mean of the conductances:

Rb,field*=L∑iHi/Rb,i*,L=∑iHi
(13.6)

Rb is combined the same way and Ra is length-weighted (read-outs). A field with one (rb,H) gets exactly the single-borehole value. The pressure drop is that of the longest loop (the shorter loops are throttled to the same flow), and the flow counts as laminar if it is laminar in any borehole. Sizing sizes the mean length and keeps the proportions,

Hi=Hi,0H¯H¯0
(13.7)

so g at fixed ln(t/ts) still depends on H¯ only through B/H¯, D/H¯ and rb/H¯ and the g-function cache interpolates as for an equal field; an equal field gets H in every borehole bit for bit as before. Applying a sized length to the design and the borehole-length study parameter use the same rule. Example: a 4 × 4 field with rows of 0.7, 0.9, 1.1 and 1.3 times the mean length has Rb,i* = 0.1172 … 0.1322 and a field value of 0.1207 m K/W; cached and exact sizing give 138.419 and 138.425 m.