Worked feature example

Ground modelling

Use the same office load on homogeneous, layered effective, layered segmented and groundwater-advection ground models.

16Boreholes
-1.92 °CMinimum mean fluid temperature
16.34 °CMaximum mean fluid temperature
5Variants compared
01 / Project

What the example does

The office field is calculated on four ground models: homogeneous ground, the same field in layered ground with effective properties, layered ground in depth segments, and homogeneous ground with groundwater flow. A fifth variant removes the geothermal heat flux.

Inputs

InputValue
Field16 boreholes, 4 × 4 rectangle, spacing 6.0 × 6.0 m
Boreholeslength 150.0 m, top 4.0 m below the surface, diameter 140 mm
Constructionsingle U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K)
Groundthermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m²
LayersClay / silt, water saturated 8 m (1.7 W/(m·K)), Sand, water saturated 17 m (2.4 W/(m·K)), Claystone / siltstone 55 m (2.2 W/(m·K)), Limestone 45 m (2.8 W/(m·K)), Granite 50 m (3.4 W/(m·K))
Fluid and flow25 % monopropylene glycol, 0.50 l/s per borehole
Loadsmonthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h
Heat pumpseasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling
Design limitsmean fluid temperature between −3.0 °C and 20.0 °C
Period25 years
Variantshomogeneous; layered, effective; layered, segmented; groundwater 10⁻⁷ m/s; no geothermal heat flux

Run the example in BoreTherm

  1. Open Design → Ground. Enter the conductivity, heat capacity, surface temperature and geothermal heat flux, or a list of layers under Layers.
  2. Choose how layers are used: effective (one average ground) or segmented (the borehole in depth segments with their own ground).
  3. For groundwater, enter the Darcy velocity and its direction under Groundwater flow.
  4. Press Calculate and compare Results → Results summary for each model.
02 / How BoreTherm calculates it

Four ways to describe the ground

1 Undisturbed temperatureTs + q_geo z / λ per layer→ mean over the borehole2 Layer propertiesthickness-weighted λ and C(effective) or per segment3 Diffusion responseg-function with theeffective diffusivity4 Groundwatermoving line source: heatcarried away downstream5 Temperaturesoffice loads superposedon the ground responseGroundwater: TfMin −0.19 °C; homogeneous −2.41 °C
Where each ground input enters the calculation.
  1. Undisturbed temperatureThe surface temperature plus the geothermal gradient (heat flux over conductivity), layer by layer. Without the heat flux the ground is 1.7 K colder at mid-depth.
  2. Layer propertiesEffective: one conductivity and heat capacity weighted by the thickness along the borehole. Segmented: every depth segment of the borehole sees its own layer.
  3. Diffusion responseThe g-function uses the thermal diffusivity λ / C.
  4. GroundwaterWith a Darcy velocity the moving finite line source replaces the pure conduction response: part of the extracted heat is resupplied by the water.
  5. TemperaturesThe same loads, years and limits for every model.
03 / In BoreTherm

The example in BoreTherm

Design → Ground with layers: the table and the profile.
Design → Ground with layers: the table and the profile.
Segmented use of the layers: every depth segment has its own ground.
Segmented use of the layers: every depth segment has its own ground.
Groundwater flow: Darcy velocity and direction.
Groundwater flow: Darcy velocity and direction.
04 / Results

Calculated results

Calculated with BoreTherm for every variant of the example. Displayed values are rounded.

Ground modelling results plotted from BoreTherm output
Chart of the BoreTherm results in the tables of this section.

Temperatures by variant

VariantBoreholesLength H [m]Tf min [°C]Tf max [°C]Rb* [m K/W]Pump [W]Design limits
layered, effective16150.000-1.91616.3350.11943,033.2within limits
groundwater flow16150.000-0.18816.0420.11943,033.2within limits
homogeneous16150.000-2.41316.0260.11943,033.2within limits
layered, segmented16150.000-2.00016.3400.11943,033.2within limits
no geothermal heat flux16150.000-3.98214.2700.11943,033.2limits exceeded
05 / Discussion

What the example shows

The differences show how sensitive this design is to the ground model; they are not evidence about real geology. Groundwater at 10⁻⁷ m/s (about 3 m per year) raises the minimum by 2.2 K. The geothermal heat flux matters as much: without it the design falls below its limit.

For a real field, take the layers from local geological data and measure the conductivity with a thermal response test.