What the example does
The office field is calculated on four ground models: homogeneous ground, the same field in layered ground with effective properties, layered ground in depth segments, and homogeneous ground with groundwater flow. A fifth variant removes the geothermal heat flux.
Inputs
| Input | Value |
|---|---|
| Field | 16 boreholes, 4 × 4 rectangle, spacing 6.0 × 6.0 m |
| Boreholes | length 150.0 m, top 4.0 m below the surface, diameter 140 mm |
| Construction | single U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K) |
| Ground | thermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m² |
| Layers | Clay / silt, water saturated 8 m (1.7 W/(m·K)), Sand, water saturated 17 m (2.4 W/(m·K)), Claystone / siltstone 55 m (2.2 W/(m·K)), Limestone 45 m (2.8 W/(m·K)), Granite 50 m (3.4 W/(m·K)) |
| Fluid and flow | 25 % monopropylene glycol, 0.50 l/s per borehole |
| Loads | monthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h |
| Heat pump | seasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling |
| Design limits | mean fluid temperature between −3.0 °C and 20.0 °C |
| Period | 25 years |
| Variants | homogeneous; layered, effective; layered, segmented; groundwater 10⁻⁷ m/s; no geothermal heat flux |
Run the example in BoreTherm
- Open Design → Ground. Enter the conductivity, heat capacity, surface temperature and geothermal heat flux, or a list of layers under Layers.
- Choose how layers are used: effective (one average ground) or segmented (the borehole in depth segments with their own ground).
- For groundwater, enter the Darcy velocity and its direction under Groundwater flow.
- Press Calculate and compare Results → Results summary for each model.
Four ways to describe the ground
- Undisturbed temperatureThe surface temperature plus the geothermal gradient (heat flux over conductivity), layer by layer. Without the heat flux the ground is 1.7 K colder at mid-depth.
- Layer propertiesEffective: one conductivity and heat capacity weighted by the thickness along the borehole. Segmented: every depth segment of the borehole sees its own layer.
- Diffusion responseThe g-function uses the thermal diffusivity λ / C.
- GroundwaterWith a Darcy velocity the moving finite line source replaces the pure conduction response: part of the extracted heat is resupplied by the water.
- TemperaturesThe same loads, years and limits for every model.
The example in BoreTherm
Calculated results
Calculated with BoreTherm for every variant of the example. Displayed values are rounded.
Temperatures by variant
| Variant | Boreholes | Length H [m] | Tf min [°C] | Tf max [°C] | Rb* [m K/W] | Pump [W] | Design limits |
|---|---|---|---|---|---|---|---|
| layered, effective | 16 | 150.000 | -1.916 | 16.335 | 0.1194 | 3,033.2 | within limits |
| groundwater flow | 16 | 150.000 | -0.188 | 16.042 | 0.1194 | 3,033.2 | within limits |
| homogeneous | 16 | 150.000 | -2.413 | 16.026 | 0.1194 | 3,033.2 | within limits |
| layered, segmented | 16 | 150.000 | -2.000 | 16.340 | 0.1194 | 3,033.2 | within limits |
| no geothermal heat flux | 16 | 150.000 | -3.982 | 14.270 | 0.1194 | 3,033.2 | limits exceeded |
What the example shows
The differences show how sensitive this design is to the ground model; they are not evidence about real geology. Groundwater at 10⁻⁷ m/s (about 3 m per year) raises the minimum by 2.2 K. The geothermal heat flux matters as much: without it the design falls below its limit.
For a real field, take the layers from local geological data and measure the conductivity with a thermal response test.