What the example does
Thirteen heat carrier fluids are compared on the office field at the same volume flow: water, two glycols, two alcohols, salt brines, glycerol, a fluid with constant properties and a temperature-dependent property table. The example shows what the fluid changes: the convection, the borehole resistance, the pressure drop and the freezing margin.
Inputs
| Input | Value |
|---|---|
| Field | 16 boreholes, 4 × 4 rectangle, spacing 6.0 × 6.0 m |
| Boreholes | length 150.0 m, top 4.0 m below the surface, diameter 140 mm |
| Construction | single U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K) |
| Ground | thermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m² |
| Fluid and flow | 25 % monopropylene glycol, 0.50 l/s per borehole |
| Loads | monthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h |
| Heat pump | seasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling |
| Design limits | mean fluid temperature between −3.0 °C and 20.0 °C |
| Period | 25 years |
| Variants | water; monoethylene and monopropylene glycol; ethanol, methanol; sodium chloride, calcium chloride, potassium acetate, carbonate and formate; glycerol; constant properties; a property table |
Run the example in BoreTherm
- Open Design → Fluid & flow. Choose the fluid and its concentration, or a table of properties against temperature.
- Read the properties at the fluid temperature, the freezing point, the Reynolds number and the pressure drop in the panel on the right.
- Press Calculate; compare Rb*, the pump power and the freezing check on Results → Results summary.
What the fluid changes
- PropertiesBoreTherm evaluates density, specific heat, conductivity and viscosity at the fluid temperature set on the Design limits & simulation page (2 °C here).
- Flow regimeThe viscous glycol is just turbulent; water at the same flow is clearly turbulent.
- ConvectionA higher Reynolds number gives a better heat transfer coefficient and a smaller pipe resistance.
- Rb*The pipe resistance enters the multipole solution; the heat capacity flow sets the short circuit between the legs.
- Pressure dropViscosity and density set the friction losses and the pump power.
- Freezing checkThe lowest inlet temperature (−3.57 °C in year 25) stays 6.2 K above the freezing point of 25 % propylene glycol (−9.8 °C).
The example in BoreTherm
Calculated results
Calculated with BoreTherm for every variant of the example. Displayed values are rounded.
Temperatures by variant
| Variant | Boreholes | Length H [m] | Tf min [°C] | Tf max [°C] | Rb* [m K/W] | Pump [W] | Design limits |
|---|---|---|---|---|---|---|---|
| calcium chloride | 16 | 150.000 | -2.372 | 15.996 | 0.1181 | 2,822.4 | within limits |
| constant properties | 16 | 150.000 | -2.395 | 16.013 | 0.1188 | 2,853.2 | within limits |
| ethanol | 16 | 150.000 | -2.423 | 16.033 | 0.1197 | 2,988.6 | within limits |
| monopropylene glycol 25 % (reference) | 16 | 150.000 | -2.413 | 16.026 | 0.1194 | 3,033.2 | within limits |
| glycerol | 16 | 150.000 | -2.492 | 16.084 | 0.1220 | 3,559.7 | within limits |
| methanol | 16 | 150.000 | -2.372 | 15.996 | 0.1181 | 2,523.6 | within limits |
| monoethylene glycol | 16 | 150.000 | -2.381 | 16.003 | 0.1184 | 2,747.8 | within limits |
| potassium acetate | 16 | 150.000 | -2.374 | 15.997 | 0.1181 | 2,852.7 | within limits |
| potassium carbonate | 16 | 150.000 | -2.363 | 15.990 | 0.1178 | 3,201.0 | within limits |
| potassium formate | 16 | 150.000 | -2.363 | 15.989 | 0.1178 | 2,789.6 | within limits |
| property table | 16 | 150.000 | -2.417 | 16.029 | 0.1196 | 3,027.5 | within limits |
| sodium chloride | 16 | 150.000 | -2.346 | 15.977 | 0.1172 | 2,707.5 | within limits |
| water | 16 | 150.000 | -2.315 | 15.954 | 0.1162 | 2,216.5 | within limits |
What the example shows
The minimum temperatures differ by less than 0.2 K between the fluids: at this flow the resistance is dominated by the grout. The pump power differs much more, from 2.2 kW with water to 3.6 kW with glycerol. Compare Reynolds number, pressure drop, pump power and freezing margin together.
Water passes the design limits here, but its inlet temperature falls below 0 °C: BoreTherm warns about freezing even when the mean temperature limits are met. The property table is a synthetic example, not a supplier data sheet.