What the example does
BoreTherm finds the borehole length at which the office field just meets its temperature limits. The example sizes the uniform 4 × 4 field and a field with unequal lengths.
Inputs
| Input | Value |
|---|---|
| Field | 16 boreholes, 4 × 4 rectangle, spacing 6.0 × 6.0 m |
| Boreholes | length 150.0 m, top 4.0 m below the surface, diameter 140 mm |
| Construction | single U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K) |
| Ground | thermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m² |
| Fluid and flow | 25 % monopropylene glycol, 0.50 l/s per borehole |
| Loads | monthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h |
| Heat pump | seasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling |
| Design limits | mean fluid temperature between −3.0 °C and 20.0 °C |
| Period | 25 years |
| Sizing range | 20 to 300 m per borehole, tolerance 0.1 m |
| Variants | uniform lengths; unequal lengths (edges longer than the centre) |
Run the example in BoreTherm
- Open Design → Design limits & simulation and check the limits and the sizing range.
- Press Size borehole length.
- Results → Required borehole length shows the length, the limiting temperature and the temperatures against the length.
- Apply length to project takes the result into the design.
How Size borehole length finds the length
- g-functionsCalculating a g-function is the expensive part, so BoreTherm calculates it exactly at five lengths and interpolates between them.
- BracketAt 20 m the limits are not met, at 300 m they are: the answer lies between.
- Brent's methodThe root of 'lowest temperature minus limit' is found on the interpolated g-function, with the ground temperature and Rb* recomputed for every length.
- Exact checkThe design is simulated again with the exact g-function at the root.
- Newton stepIf the exact result is not within the tolerance, a secant step through the exact points gives the next length.
The example in BoreTherm
Calculated results
Calculated with BoreTherm for every variant of the example. Displayed values are rounded.
| Variant | Required mean H [m] | Total [m] | Tf min [°C] | Tf max [°C] | Binding limit | Iterations |
|---|---|---|---|---|---|---|
| uniform 150 m (input) | 143.718 | 2,299.484 | -2.998 | 16.178 | minimum temperature | 12 |
| unequal lengths | 143.282 | 2,292.519 | -2.998 | 16.195 | minimum temperature | 12 |
Temperatures by variant
| Variant | Boreholes | Length H [m] | Tf min [°C] | Tf max [°C] | Rb* [m K/W] | Pump [W] | Design limits |
|---|---|---|---|---|---|---|---|
| uniform 150 m (input) | 16 | 150.000 | -2.413 | 16.026 | 0.1194 | 3,033.2 | within limits |
| uniform, sized | 16 | 143.718 | -2.998 | 16.178 | 0.1190 | 2,906.2 | within limits |
| unequal lengths | 16 | 146.250 | -2.715 | 16.120 | 0.1192 | 3,033.2 | within limits |
What the example shows
The uniform field needs 143.72 m per borehole (2,299 m in total), 4 % less than the 150 m of the input. The minimum temperature limit is binding; the maximum stays at 16.2 °C. With unequal lengths the field needs 143.28 m on average: longer boreholes at the edge, where the ground is less disturbed, help slightly.
Sizing never changes the limits or the search range. The result is a proposal until it is applied to the project.