What the example does
The 16 boreholes of the office field are connected in three ways: all in parallel (the reference), in pairs in series, and as explicitly connected strings of unequal length. The total flow is the same. The example shows how the connection changes the flow per borehole, the resistance and the pump pressure.
Inputs
| Input | Value |
|---|---|
| Field | 16 boreholes, 4 × 4 rectangle, spacing 6.0 × 6.0 m |
| Boreholes | length 150.0 m, top 4.0 m below the surface, diameter 140 mm |
| Construction | single U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K) |
| Ground | thermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m² |
| Fluid and flow | 25 % monopropylene glycol, 0.50 l/s per borehole |
| Loads | monthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h |
| Heat pump | seasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling |
| Design limits | mean fluid temperature between −3.0 °C and 20.0 °C |
| Period | 25 years |
| Variants | 16 in parallel; 8 strings of 2 in series; connected strings of unequal length |
Run the example in BoreTherm
- Open Design → Field layout and switch the edit mode to Connect. Draw strings from the header through the boreholes.
- On Design → Fluid & flow the network shows the flow and pressure drop of every string.
- Press Calculate; Results → Results summary lists the network.
Flow distribution in the network
- StringsEach string is a chain of boreholes; the strings are connected in parallel to the header.
- Flow splitAll strings see the same pressure difference, so a long string gets less flow.
- Per boreholeIn pairs, each borehole carries the flow of a string: twice the parallel flow.
- ResistanceMore flow per pipe gives turbulent flow and a lower Rb* (0.114 instead of 0.119).
- Field responseThe outlet of one borehole is the inlet of the next.
- PumpThe pressure drop grows with the square of the velocity and the length of the string.
The example in BoreTherm
Calculated results
Calculated with BoreTherm for every variant of the example. Displayed values are rounded.
Temperatures by variant
| Variant | Boreholes | Length H [m] | Tf min [°C] | Tf max [°C] | Rb* [m K/W] | Pump [W] | Design limits |
|---|---|---|---|---|---|---|---|
| all in parallel | 16 | 150.000 | -2.413 | 16.026 | 0.1194 | 3,033.2 | within limits |
| pairs in series | 16 | 150.000 | -2.237 | 15.897 | 0.1137 | 20,060.1 | within limits |
| strings of unequal length | 16 | 150.000 | -2.207 | 15.876 | 0.1127 | 43,033.1 | within limits |
What the example shows
The series connections improve the minimum temperature only slightly (by 0.2 K) but need much more pump power: 20 kW for pairs and 43 kW for the longest strings, against 3 kW in parallel. Check the flow and resistance of every string, not only the field-average temperature.