HomeFeaturesExamplesTutorialsHelpTheoryVerificationPricingContact
BoreTherm / Example libraryExample 11 / 23
Worked feature example

Site planning

An L-shaped site contains a drilling boundary, setbacks, a building, trees, a sewer corridor and a connection point. Check the existing field and generate fill patterns inside the usable area.

16Boreholes
-1.13 °CMinimum mean fluid temperature
16.42 °CMaximum mean fluid temperature
5Variants compared
01 / Project

What the example does

An office on an L-shaped plot: a drawing gives the drilling boundary, the building, trees, a sewer corridor and the connection point. BoreTherm checks the existing 16-borehole field against the setbacks and fills the usable area with four patterns.

Inputs

InputValue
Field16 boreholes, free positions
Boreholeslength 150.0 m, top 4.0 m below the surface, diameter 140 mm
Constructionsingle U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K)
Groundthermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m²
Fluid and flow25 % monopropylene glycol, 0.50 l/s per borehole
Loadsmonthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h
Heat pumpseasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling
Design limitsmean fluid temperature between −3.0 °C and 20.0 °C
Period25 years
Siteplot from a DXF drawing, building, trees, sewer corridor, connection point; setbacks from each object

Run the example in BoreTherm

  1. Open Design → Field layout and switch the view to Site. Import the drawing and assign its layers: plot, building, obstacles, connection point.
  2. Set the setbacks; the usable drilling area is shaded.
  3. Check site lists every violation of a setback; Fill area places a pattern in the usable area.
  4. Press Calculate for the field on the plot.
02 / How BoreTherm calculates it

From the drawing to a field

1 Drawingplot, building, trees,sewer, connection point2 Setbacksoffset every object by itsdistance → forbidden zones3 Usable areaplot minus zones→ 1,168 m² for drilling4 Fillgrid, staggered, row-wise orperimeter positions5 Selection16 heads nearest theconnection point6 Trenchshortest connection fromthe heads → 110 mGrid fill: 28 positions, 16 used, 110 m trench
The site check and the fill, with the numbers of the grid pattern.
  1. DrawingThe layers of the DXF drawing become site objects.
  2. SetbacksEach object gets a distance it must keep from boreholes.
  3. Usable areaWhat remains of the plot is the drilling area.
  4. FillThe pattern generator places positions at the minimum spacing inside the area.
  5. SelectionThe positions closest to the connection point are taken first.
  6. TrenchThe trench length is estimated from the heads to the connection point.
03 / In BoreTherm

The example in BoreTherm

Site view of the Field layout page: plot, objects and setbacks.
Site view of the Field layout page: plot, objects and setbacks.
Fill area: the pattern and the number of boreholes.
Fill area: the pattern and the number of boreholes.
The site check: no violations for the existing field.
The site check: no violations for the existing field.
04 / Results

Calculated results

Calculated with BoreTherm for every variant of the example. Displayed values are rounded.

Site-check quantityValue
Valid fieldYes
Drilling area [m²]1,168.164
Trench [m]110.460
Violations0
Fill patternCapacity [positions]Selected headsTrench [m]
grid2816110.460
staggered3216124.339
rowwise3016116.647
perimeter2216124.700
Site planning results plotted from BoreTherm output
Chart of the BoreTherm results in the tables of this section.

Temperatures by variant

VariantBoreholesLength H [m]Tf min [°C]Tf max [°C]Rb* [m K/W]Pump [W]Design limits
existing field16150.000-1.13016.4160.11943,033.2within limits
grid fill16150.000-1.13016.4160.11943,033.2within limits
perimeter fill16150.000-0.55116.4750.11943,033.2within limits
row-wise fill16150.000-1.11216.4340.11943,033.2within limits
staggered fill16150.000-0.97516.4230.11943,033.2within limits
05 / Discussion

What the example shows

All four fills keep 16 boreholes and the 150 m length, so their temperatures differ only by the arrangement: the perimeter pattern spreads the boreholes along the edge and is the warmest. The grid pattern needs the shortest trench.

The setbacks are input assumptions. A site check does not establish a drilling permit or environmental compliance.