What the example does
Is the ground-source heat pump the best choice for the office? BoreTherm compares it with an air-source heat pump, gas and oil condensing boilers, a pellet boiler, district heating and a hybrid of air-source heat pump and gas boiler, for the same heating, hot water and cooling.
Inputs
| Input | Value |
|---|---|
| Field | 16 boreholes, 4 × 4 rectangle, spacing 6.0 × 6.0 m |
| Boreholes | length 150.0 m, top 4.0 m below the surface, diameter 140 mm |
| Construction | single U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K) |
| Ground | thermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m² |
| Fluid and flow | 25 % monopropylene glycol, 0.50 l/s per borehole |
| Loads | monthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h |
| Heat pump | seasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling |
| Design limits | mean fluid temperature between −3.0 °C and 20.0 °C |
| Period | 25 years |
| Comparison | German data set 2026-10: prices, efficiencies, service lives and emission factors; 20 years; real prices, gross |
Run the example in BoreTherm
- Open Economics → Heating-system comparison and switch the comparison on. Choose the systems, the period, the interest and the data scenario.
- Press Calculate: the comparison is calculated with the design.
- Results → System comparison shows the annual cost, the cumulative cost, CO₂, primary energy and the assumptions with their sources.
How the systems are compared
- Same serviceEvery system covers the same useful heat, hot water and cooling.
- Energy per systemThe ground-source heat pump uses the seasonal performance factor from the borefield simulation (4.66 including auxiliaries).
- InvestmentThe ground-source system includes the borefield estimate.
- AnnuityInvestment converted into a yearly cost with the interest and service life, plus energy and maintenance.
- Cost of heatThe annuity divided by the heat delivered.
- EmissionsTwo conventions: the statutory factors and the real emissions.
The example in BoreTherm
Calculated results
Calculated with BoreTherm for every variant of the example. Displayed values are rounded.
Application assumption dataset: DE 2026-10; data date 2026-10-18.
| System | Annual annuity [EUR/a] | LCOH heat [EUR/kWh] | SPF total | Statutory CO₂ [t/a] | Real CO₂ [t/a] |
|---|---|---|---|---|---|
| BHE heat pump | 34,154.46 | 0.1544 | 4.663 | 29.065 | 17.854 |
| Air/water heat pump | 31,733.50 | 0.1374 | 4.445 | 32.504 | 19.967 |
| Gas condensing boiler | 40,299.03 | 0.1657 | 0.000 | 59.284 | 43.780 |
| Oil condensing boiler | 45,291.84 | 0.1897 | 0.000 | 76.645 | 63.984 |
| Pellet boiler | 35,501.60 | 0.1426 | 0.000 | 12.018 | 4.543 |
| District heating | 41,036.40 | 0.1692 | 0.000 | 45.460 | 36.294 |
| Hybrid air/water heat pump and gas boiler | 40,269.08 | 0.1655 | 0.000 | 37.019 | 22.924 |
Temperatures by variant
| Variant | Boreholes | Length H [m] | Tf min [°C] | Tf max [°C] | Rb* [m K/W] | Pump [W] | Design limits |
|---|---|---|---|---|---|---|---|
| office reference | 16 | 150.000 | -2.413 | 16.026 | 0.1194 | 3,033.2 | within limits |
What the example shows
With these 2026 assumptions the air-source heat pump has the lowest annual cost (31,734 EUR/a); the ground-source heat pump follows (34,154 EUR/a) with the best efficiency and lower CO₂ than the air-source heat pump. The result depends on the stated tariffs, efficiencies, service lives and emission factors; the low and high scenarios of the data set show how much.
The data set and its date are part of every result. Grants and compliance with national rules need verified data.