16Boreholes
-2.41 °CMinimum mean fluid temperature
16.03 °CMaximum mean fluid temperature
1Variants compared
01 / Project
What the example does
The office field is calculated and sized, and the results are exported: tables as CSV, the g-function, charts as images, and a report as PDF, HTML or Markdown with the inputs, the results and the charts.
Inputs
| Input | Value |
|---|---|
| Field | 16 boreholes, 4 × 4 rectangle, spacing 6.0 × 6.0 m |
| Boreholes | length 150.0 m, top 4.0 m below the surface, diameter 140 mm |
| Construction | single U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K) |
| Ground | thermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m² |
| Fluid and flow | 25 % monopropylene glycol, 0.50 l/s per borehole |
| Loads | monthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h |
| Heat pump | seasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling |
| Design limits | mean fluid temperature between −3.0 °C and 20.0 °C |
| Period | 25 years |
Run the example in BoreTherm
- Press Calculate and Size borehole length.
- Every chart has buttons for PNG, SVG, PDF and CSV; tables export to CSV.
- Press Report: choose the sections, the language and the format, then preview or generate.
- Results → Results summary collects the key figures in one page.
02 / How BoreTherm calculates it
From the calculation to the report
- ResultsEverything calculated in the session can go into the report.
- SectionsA section appears only when its result exists; results from earlier inputs are marked.
- ChartsCharts are drawn for the report, not copied from the screen.
- FormatsPDF for sending, HTML and Markdown for further editing.
- RecordEvery report states the inputs, the date and every warning.
03 / In BoreTherm
The example in BoreTherm
04 / Results
Calculated results
Calculated with BoreTherm for every variant of the example. Displayed values are rounded.
Temperatures by variant
| Variant | Boreholes | Length H [m] | Tf min [°C] | Tf max [°C] | Rb* [m K/W] | Pump [W] | Design limits |
|---|---|---|---|---|---|---|---|
| office reference | 16 | 150.000 | -2.413 | 16.026 | 0.1194 | 3,033.2 | within limits |
05 / Discussion
What the example shows
The report is the calculation record of a design: it shows the inputs, the methods, the results and every warning. The exports serve further work: CSV for spreadsheets, the g-function for other tools, images for documents.