HomeFeaturesExamplesTutorialsHelpTheoryVerificationPricingContact
BoreTherm / Example libraryExample 21 / 23
Worked feature example

Results and reports

Calculate and size the office field, export CSV and g-function data, and create native PDF, HTML and Markdown reports with embedded charts.

16Boreholes
-2.41 °CMinimum mean fluid temperature
16.03 °CMaximum mean fluid temperature
1Variants compared
01 / Project

What the example does

The office field is calculated and sized, and the results are exported: tables as CSV, the g-function, charts as images, and a report as PDF, HTML or Markdown with the inputs, the results and the charts.

Inputs

InputValue
Field16 boreholes, 4 × 4 rectangle, spacing 6.0 × 6.0 m
Boreholeslength 150.0 m, top 4.0 m below the surface, diameter 140 mm
Constructionsingle U, PE pipe 32 × 2.9 mm, shank spacing 70 mm, grout 1.60 W/(m·K)
Groundthermal conductivity 2.60 W/(m·K), heat capacity 2.20 MJ/(m³·K), surface temperature 9.0 °C, geothermal heat flux 0.060 W/m²
Fluid and flow25 % monopropylene glycol, 0.50 l/s per borehole
Loadsmonthly: heating 200 MWh, hot water 8 MWh and cooling 45 MWh per year; peaks 100 kW heating and 45 kW cooling for 6 h
Heat pumpseasonal performance factors 3.8 heating, 2.8 hot water, 5.0 cooling
Design limitsmean fluid temperature between −3.0 °C and 20.0 °C
Period25 years

Run the example in BoreTherm

  1. Press Calculate and Size borehole length.
  2. Every chart has buttons for PNG, SVG, PDF and CSV; tables export to CSV.
  3. Press Report: choose the sections, the language and the format, then preview or generate.
  4. Results → Results summary collects the key figures in one page.
02 / How BoreTherm calculates it

From the calculation to the report

1 Resultstemperatures, sizing, costs,comparison, studies2 Sectionsonly those with results;stale results marked3 Chartsdrawn again for the pagesize of the report4 FormatsPDF, HTML or Markdown,same content5 Recordinputs, version, date andwarnings in every reportOne report: inputs, results, charts and warnings
The report collects what was calculated, with the inputs that produced it.
  1. ResultsEverything calculated in the session can go into the report.
  2. SectionsA section appears only when its result exists; results from earlier inputs are marked.
  3. ChartsCharts are drawn for the report, not copied from the screen.
  4. FormatsPDF for sending, HTML and Markdown for further editing.
  5. RecordEvery report states the inputs, the date and every warning.
03 / In BoreTherm

The example in BoreTherm

Results → Results summary of the calculated office.
Results → Results summary of the calculated office.
The summary with the borehole sections.
The summary with the borehole sections.
The Report dialog: sections, language and format.
The Report dialog: sections, language and format.
04 / Results

Calculated results

Calculated with BoreTherm for every variant of the example. Displayed values are rounded.

Results and reports results plotted from BoreTherm output
Chart of the BoreTherm results in the tables of this section.

Temperatures by variant

VariantBoreholesLength H [m]Tf min [°C]Tf max [°C]Rb* [m K/W]Pump [W]Design limits
office reference16150.000-2.41316.0260.11943,033.2within limits
05 / Discussion

What the example shows

The report is the calculation record of a design: it shows the inputs, the methods, the results and every warning. The exports serve further work: CSV for spreadsheets, the g-function for other tools, images for documents.