Source, inputs and purpose
Source. Bonin, J. (2015). Heat Pump Planning Handbook. Routledge. Task 15.2 (p. 252) and its solution 18.2, pp. 276–283; lock-out §5.2.5 (p. 97); candidates from Table 5.12 (p. 123) and Tables 18.3 / 18.4 (pp. 277, 280).
Inputs and reference results are taken from the cited publication; BoreTherm results were calculated with BoreTherm on the project rebuilt from those inputs; differences are explained below.
What the example checks
The example is about choosing the heat pump, not about the ground: which unit covers the heating and hot water load, whether the field’s brine flow reaches the unit’s minimum, whether the buffer is large enough, and what pump head the brine circuit needs. A variant adds a daily utility lock-out.
Inputs
Values marked Assumption are not given in the book and were chosen for the BoreTherm project; the others are the book’s, with the section or page.
| Input | Value | Source |
|---|---|---|
| Heating load | 45 W/m² × 274 m² = 12.33 kW; domestic hot water 4 × 0.3 kW = 1.2 kW; monovalent | 18.2 |
| Heating system | underfloor heating, 35 °C flow, design outdoor temperature −12 °C | 18.2 |
| Borehole heat exchangers | four double U of 85–90 m (the project uses 4 × 88 m), specific extraction 35 W/m | 18.2 |
| Brine flow | 3.9 m³/h, the minimum flow of the SW 15.000 | 18.2 |
| Hydraulics | header and connection pipes 0.15 bar + fittings 0.07 bar (22 kPa); free-cooling heat exchanger 0.20 bar | p. 279 |
| Buffer | 300 l | 18.2 |
| Candidates, B0/W35 | GeoMax SW 10.300 / 12.400 / 15.000 / 16.800: 10.3 / 12.4 / 15.0 / 16.8 kW, COP 4.2 / 4.2 / 4.4 / 4.4 | Table 5.12 |
| Candidates, minimum brine flow | 2.6 / 3.2 / 3.9 / 4.4 m³/h | Tables 18.3, 18.4 |
| Candidates, evaporator pressure drop | 0.20 / 0.18 / 0.17 / 0.21 bar at those flows | Tables 18.3, 18.4 |
| Ground | 1.8 W/(m·K), 2.2 MJ/(m³·K), 10 °C | Assumption |
| Field and boreholes | 4 × 88 m in a row at 6 m, 150 mm, PE 32 × 2.9 mm, grout 2.0 W/(m·K), 25 % monoethylene glycol | Assumption |
| Loads over the year | heating 20.3 MWh/a with the monthly shape of a German single-family house, hot water 4.0 MWh/a, free cooling 2 MWh/a | Assumption |
| Efficiency and limits | fixed seasonal performance factor 4.4; minimum mean fluid temperature −3 °C | Assumption |
| Lock-out variant | 231 m² → 10.4 kW, hot water 1.4 kW, 4 h lock-out per day (factor 1.2); brine flow 4.4 m³/h | §5.2.5, p. 97; flow: Assumption |
Run the example in BoreTherm
- Open the brine/water heat pump reference project (or its lock-out variant) from the examples folder (File → Open).
- Press Calculate, open Design → Heat pump → Selection results and click Check candidates.
How the heat pump is checked
- RequirementHeating load plus hot water, monovalent.
- CapacityEach unit's capacity at the design point against the requirement.
- Brine flowThe SW 16.800 needs 4.4 m³/h; the field delivers 3.9 m³/h.
- BufferThe minimum buffer volume of each unit.
- Pump headThe brine pump must overcome the field, header, heat exchanger and evaporator.
- Coupled rerunThe field is simulated again with each unit's efficiency.
The example in BoreTherm
Calculated results
Displayed values are rounded. Differences are BoreTherm relative to the book unless stated otherwise.
| Quantity | Book | BoreTherm | Difference |
|---|---|---|---|
| Required heating capacity | 13.5 kW | 13.53 kW | equal |
| SW 10.300 / SW 12.400, capacity | – | −23.9 % / −8.4 %, not met | – |
| SW 15.000, capacity | chosen | +10.9 %, met; overall Tight | same choice |
| SW 16.800 | – | +24.2 % capacity; overall not met: field flow 11.4 % below its 4.4 m³/h minimum | – |
| Buffer for the SW 15.000 | 300 l | at least 0.215 m³ needed: met | consistent |
| Brine pump head for the SW 15.000 | 0.71 bar printed; 0.81 bar with the loop loss corrected | 66.6 kPa = field 7.6 + header 22.0 + heat exchanger 20.0 + evaporator 17.0 | −18 % against 0.81 bar |
| Total borehole length | 343 m (rule of thumb with 35 W/m) | 264 m (4 × 66.1 m) on the assumed ground | −23 % |
Lock-out variant
Section 5.2.5: a smaller house with 4 hours of utility lock-out per day.
| Quantity | Book | BoreTherm | Difference |
|---|---|---|---|
| Required heating capacity | (10.4 + 1.4) × 1.2 = 14.2 kW | 14.16 kW | equal (printed rounded) |
| SW 15.000 | chosen as the next size | +5.9 %, Tight | same choice |
| SW 16.800 | – | +18.6 %, met; overall Tight | – |
| Brine pump head for the SW 15.000 at 4.4 m³/h | – | 72.2 kPa | – |
Why the results differ
Capacity and selection
The capacity statuses follow from the book’s load and catalogue numbers, so BoreTherm reaches the same choice. The SW 16.800 has enough capacity, but its minimum brine flow is 4.4 m³/h while this field is designed for the 3.9 m³/h of the SW 15.000, so BoreTherm rates it not met. In the lock-out variant the field runs at 4.4 m³/h (an assumption) so that both larger units are compared on capacity alone.
The chosen SW 15.000 is rated Tight overall, from checks the book does not make: the design source temperature lies outside the datasheet’s rated range, the estimated part-load profile favours a modulating unit, and its efficiency at the 1.1 °C design source (COP 4.52) draws 0.8 % more heat from the ground than the seasonal factor the field was simulated with.
Pump head
The whole difference lies in the borehole loop. The flow in the loops is laminar (Reynolds number about 1,850 with 25 % glycol near 0 °C), and BoreTherm’s 7.6 kPa matches the laminar hand formula (7.7 kPa). The book uses a tabulated planning value of 1.2 m per 100 m over 180 m, 22 kPa. With the book’s loop loss, BoreTherm’s sum is 0.81 bar exactly. The book calculates the loop loss as 0.22 bar on p. 279 but adds 0.12 bar in its total, which is why it prints 0.71 bar.
Length
The book sizes the boreholes with a specific extraction rate (35 W/m for 1,800 hours a year), a rule of thumb. BoreTherm simulates the field on an assumed ground, so the −23 % says only that the rule is conservative for that ground. At the book’s 4 × 88 m, BoreTherm’s minimum mean fluid temperature is −0.05 °C.
BoreTherm features exercised
- Heat pump selection: requirement sheet, minimum brine flow, buffer rule, brine pump head with evaporator and free-cooling heat exchanger
- Borehole construction (double U)
- Automatic sizing