HomeFeaturesExamplesTutorialsHelpTheoryVerificationPricingContact
Theory manual

2. Nomenclature

2.1 Latin symbols

Table 2. Latin symbols.
SymbolQuantityUnit
Bborehole spacing (centre to centre)m
Cvvolumetric heat capacity of the ground, ρcJ/(m³ K)
cpspecific heat capacity of the fluidJ/(kg K)
Dburied depth of the borehole topm
d, dijhorizontal distance between boreholes (segments)m
diinner pipe diameter; Dh hydraulic diameterm
E1exponential integral–
fDarcy friction factor–
gthermal response factor (g-function)–
Hactive borehole lengthm
hconvective heat transfer coefficientW/(m² K)
hijsegment-to-segment response factor–
Jmultipole order–
Ltotal active length of the field, ∑Him
ṁcpheat capacity flow (one borehole unless stated)W/K
Nnumber of boreholes; number of time steps–
Nu, Pr, ReNusselt, Prandtl and Reynolds numbers–
Ppump electric powerW
Qheat rate of the field (+ injection)W
qheat rate per metre of borehole (+ injection)W/m
qgeogeothermal heat fluxW/m²
Rblocal borehole thermal resistance, fluid to borehole wallm K/W
Rb*effective borehole resistance (with leg-to-leg short-circuit)m K/W
Rainternal (leg-to-leg) resistancem K/W
Rppipe resistance: convection + wall + contact, one pipem K/W
rb, ri, roborehole radius; inner and outer pipe radiusm
sshank spacing (opposite legs); integration variablem; 1/m
Tb, Tf, Tmborehole-wall, mean fluid and undisturbed ground temperature°C
Tin, Toutfluid temperature entering and leaving the field°C
Tsmean ground surface temperature°C
t, ts, tptime; Eskilson's characteristic time; peak durations
V˙volume flowm³/s

2.2 Greek symbols and subscripts

Table 3. Greek symbols, subscripts and abbreviations.
SymbolQuantityUnit
αthermal diffusivity of the ground, λ/Cvm²/s
βdimensionless pipe resistance 2πλgRp–
εabsolute pipe roughnessm
ηpump efficiency; Hellström's short-circuit parameter–
λ, λg, λp, λfconductivity of ground, grout, pipe wall and fluidW/(m K)
μdynamic viscosity of the fluidPa s
ρdensity of the fluidkg/m³
σconductivity contrast (λg−λ)/(λg+λ)–
κload-aggregation weight–
b, f, pborehole wall, fluid, pipe
ext, injextraction (heating), injection (cooling)
UHTR, UBWTuniform heat transfer rate, uniform borehole-wall temperature
UHFuniform heat flux (Rb* formula)
Table 4. Symbols of Chapters 11–17.
SymbolQuantityUnit
u, vTDarcy velocity (specific discharge); heat-transport velocitym/s
PePéclet number vTH/α–
φflow direction; borehole azimuth (from +x towards +y)rad
θborehole tilt from the verticalrad
Hvvertical extent of the active lengthm
Ri, Rparlocal resistance of segment i (UFT); parallel resistance of the fieldm K/W
g1, g2, g12conductances of the down- and up-going channels to the wall and between themW/(m K)
gc, δgcombined short-time response; capacity correction–
ΔPs, Kpressure drop of a string; minor-loss coefficientPa; –
c(𝐩)clearance of a position in the site planm
T0undisturbed ground temperature of a thermal response test°C
τbtime constant of the borehole resistance term (TRT)s
neff, r1effective number of observations; lag-1 autocorrelation of the residuals–
FoFourier number αt/rb2–

2.3 Conventions

tmonth=8760h12=730h=2.628·106s
(2.1)