7. Loads

7.1 Monthly loads (classic style)

The building loads are given as monthly energies for space heating Eh, domestic hot water Edhw and cooling Ec [MWh per 730 h month], and converted to ground loads with seasonal performance factors, as in the classic monthly method. Heat extracted from the ground is the delivered heat minus the compressor work; heat injected is the cooling plus the compressor work:

Eext=EhSPFh−1SPFh+EdhwSPFdhw−1SPFdhw
(7.1)
Einj=EcSPFc+1SPFc(heat pump),Einj=Ec(direct cooling)
(7.2)

When the inputs are given directly as ground loads, the factors are ignored. The mean ground heat rate of month c (+ injection) is

Qc=(Einj,c−Eext,c)·3.6·109J/MWh730·3600s,qc=QcL
(7.3)

For the example (SPF 3.8 heating, 2.8 DHW, 5.0 cooling) the factors are 0.7368, 0.6429 and 1.20, giving 152.5 MWh/year extracted and 54.0 MWh/year injected. The conversion was verified against the worked example of the classic method's published manual (4.50 MWh at SPF 2.12 gives 2.377 MWh). SPF values must be at least 1 (heating, DHW) and positive (cooling).

When only annual energies are known, the classic monthly method distributes them with default monthly profiles; the example project uses them (Table 14).

Table 14. Default monthly profiles of the classic method (fractions of the annual energy) used by the example project.
JanFebMarAprMayJunJulAugSepOctNovDec
Heating0.1550.1480.1250.0990.0640.0000.0000.0000.0610.0870.1170.144
Cooling0.0000.0000.0000.0250.0750.2000.4000.2500.0500.0000.0000.000

7.2 Peak loads

Each month may carry one heating and one cooling peak, given as a building power [kW] with a duration tp [h, at most 730]. The same SPF factors apply, as in the classic monthly conventions:

Qpeak,ext=−PhSPFh−1SPFh,Qpeak,inj=PcSPFc+1SPFc
(7.4)

DHW does not enter the peak. A peak affects the result only if it is more extreme than the base load of the month in its direction; a month without an effective peak reports the base temperature.

7.3 Hourly loads

In hourly mode the building loads are hourly powers [kW] for heating, cooling and DHW (8760 values, repeated every year, or 8760 × years values), read from the project or from a CSV file with one row per hour and columns heating[, cooling[, dhw]] (header optional; ';', tab or ',' separated). The hourly ground heat rate is

Qn=Pc,nSPFc+1SPFc−Ph,nSPFh−1SPFh−Pdhw,nSPFdhw−1SPFdhw
(7.5)

In the hourly mode of the classic method, monthly peaks are placed in the last tp hours of each month; an hourly profile can be built from monthly data in the same way.