Source, inputs and purpose
Source. Kavanaugh, S. and Rafferty, K. (2014). Geothermal Heating and Cooling: Design of Ground-Source Heat Pump Systems. ASHRAE, Atlanta. Chapter 4, §4.2, design steps 1–10, pp. 93–110 (results on p. 110).
Inputs and reference results are taken from the cited publication; BoreTherm results were calculated with BoreTherm on the project rebuilt from those inputs; differences are explained below.
What the example checks
A small cooling-dominated field in a moderate climate. The book designs it step by step with the ASHRAE equation and a tabulated long-term penalty. The comparison shows how BoreTherm’s calculated interference of a 2 × 5 field compares with that penalty, for the cooling length and, separately, for the heating length.
Inputs
Values marked Assumption are not given in the book and were chosen for the BoreTherm project; the others are the book’s, with the section or page.
| Input | Value | Source |
|---|---|---|
| Building | 930 m² office, north cluster of four water-to-air heat pumps | pp. 93–99 |
| Block loads | 35.75 kW cooling, 18.76 kW heating | Ch. 4 |
| Heat pump efficiency (fixed) | EER 13.8 Btu/Wh (COPc 4.04), COPh 4.0 | Ch. 4 |
| Equivalent full-load hours, part-load factors | 890 h cooling, 755 h heating; 0.32 and 0.31 | Ch. 4 |
| Ground | 2.25 W/(m·K), diffusivity 0.85 ft²/day (2.46 MJ/(m³·K)), 15 °C (response test) | Ch. 4 |
| Borehole | 130 mm, single U 32 mm DR 11, grout 1.56 W/(m·K) | Ch. 4 |
| Borehole resistance | 0.110 m·K/W, imposed as Rb* | Ch. 4 |
| Fluid and flow | water, 117 L/min | Ch. 4 |
| Design period and peaks | 20 years, 4 h peaks | Ch. 4 |
| Length per borehole in the project | 78 m (the book’s 77.1 m rounded up) | p. 110 |
| Field geometry | 2 × 5 boreholes at 6.1 m (20 ft); the layout is not given in the text | Assumption |
| Sizing criteria | mean fluid temperature ≤ 32.8 °C and ≥ 8.3 °C (means of the book’s entering and leaving temperatures) | Assumption |
| Monthly loads | July cooling 8.51 MWh, January heating 4.33 MWh; other months by an approximate St. Louis degree-day shape | Assumption |
| Peak months | 35.75 kW cooling in July, 18.76 kW heating in January | Assumption |
Run the example in BoreTherm
- Open the St. Louis reference project from the examples folder (File → Open).
- Press Size borehole length and open Results → Required borehole length.
Two ways to the length
- Same loadsThe north cluster's block loads and full-load hours.
- Ground responseCylinder source pulses in the book; the g-function of the 2 × 5 field in BoreTherm.
- Long-term warming+2.2 K from the table against BoreTherm's calculated warming.
- LengthCooling sets the length in both.
The example in BoreTherm
Calculated results
Displayed values are rounded. Differences are BoreTherm relative to the book unless stated otherwise.
| Quantity | Book | BoreTherm | Difference |
|---|---|---|---|
| Cooling length, 10 boreholes | 771 m (10 × 77.1 m) | 721 m (10 × 72.1 m) | −6.5 % |
| Same, BoreTherm’s classic-method sizing options | 771 m | 716 m (10 × 71.6 m) | −7.1 % |
| Heating length | 543 m | 500 m (10 × 50.0 m) | −7.9 % |
| Mean fluid temperature at 78 m | criteria 8.3 / 32.8 °C | 10.70 / 31.53 °C | within both limits |
Why the results differ
Why BoreTherm is shorter
The book adds a long-term temperature penalty of +2.2 K, read from a table for a 20 ft grid with mild groundwater recharge, and a short-circuit factor of 1.04. BoreTherm calculates the long-term warming of the actual 2 × 5 field from its g-function. For this small, moderately unbalanced field that warming is smaller than the tabulated penalty, so BoreTherm needs 6.5 % less length for cooling.
For heating, the book takes the first year with no annual imbalance and no penalty. In this cooling-dominated field the coldest month is indeed in the first year; BoreTherm still needs 7.9 % less, which reflects the different treatment of the peak and monthly pulses.
What is not compared
The units are water-to-air heat pumps, so BoreTherm’s brine/water candidate check does not apply. The book first designs eight boreholes (766 m) and then redesigns for ten; the comparison uses the ten-borehole design.