Source, inputs and purpose
Source. Chiasson, A.D. (2016). Geothermal Heat Pump and Heat Engine Systems: Theory and Practice. Wiley / ASME Press. Example 10.1, pp. 290–292, and Example 10.2, pp. 292–294, with the branch and fitting sheets Figs. E.10.2b and E.10.2c (p. 294).
Inputs and reference results are taken from the cited publication; BoreTherm results were calculated with BoreTherm on the project rebuilt from those inputs; differences are explained below.
What the example checks
The pressure drop of a larger field with water in fully turbulent flow, along the path to the farthest borehole, and the fluid power the circulation pump must deliver.
Inputs
Values marked Assumption are not given in the book and were chosen for the BoreTherm project; the others are the book’s, with the section or page.
| Input | Value | Source |
|---|---|---|
| Field | 32 boreholes, 4 × 8 at 20 ft (6.1 m), 250 ft (76.2 m) deep | Ex. 10.1 |
| Flow | 160 gpm in total (10.09 L/s), 5 gpm per borehole; four circuits in reverse return | Ex. 10.2 |
| U-tubes and fluid | 1 in. SDR 11; water at 50 °F (10 °C) | Ex. 10.2 |
| Book path to the farthest borehole | U-tube branch with 20 ft of lateral (520 ft): 8.55 ft pipe + 0.14 ft fittings; headers and mains: 2.48 ft | Fig. E.10.2b |
| Header pressure drop in the project | 2.48 + 0.14 + 0.33 ft (the lateral) = 2.95 ft = 8.8 kPa | from Fig. E.10.2b |
| Pipe roughness | 1 µm | Assumption |
| Thermal side | ground and loads of Example 6.5 scaled to this field, Rb 0.15 m·K/W (they only illustrate) | Assumption |
Run the example in BoreTherm
- Open the 32-borehole pressure drop reference project from the examples folder (File → Open).
- Press Calculate, open Design → Heat pump → Selection results and click Calculate equipment requirements for the requirement sheet.
How the pump head adds up
- Flow per boreholeReverse return gives every borehole the same flow.
- ReynoldsFully turbulent: the friction factors of the book and BoreTherm are close.
- U-tube lossBoreTherm's field pressure drop over twice the borehole length.
- HeaderThe book's mains, headers, fittings and lateral entered as the header pressure drop.
- Pump headThe sum, and with the flow the fluid power.
The example in BoreTherm
Calculated results
Displayed values are rounded. Differences are BoreTherm relative to the book unless stated otherwise.
| Quantity | Book | BoreTherm | Difference |
|---|---|---|---|
| U-tube Reynolds number | 1.13 × 10⁴ | 11,243 | −0.5 % |
| U-tube pipe loss over 500 ft | 8.55 ft × 500 / 520 = 24.6 kPa | 24.2 kPa | −1.3 % |
| Header, mains, fittings and lateral | 2.95 ft = 8.8 kPa | input | – |
| Total pump head | 11.16 ft = 33.4 kPa | 33.0 kPa | −0.9 % |
| Fluid power | 0.45 hp = 336 W | 33.0 kPa × 10.09 L/s = 333 W | −0.6 % |
Why the results differ
Mapping the book’s path
BoreTherm’s field pressure drop is the U-tube loop over twice the borehole length. The book’s U-tube branch also contains 20 ft of lateral to the header (520 ft in total). The project therefore moves the lateral’s share, together with the headers, mains and fittings, into the header pressure drop of the heat pump selection. On the same 500 ft, the U-tube losses agree within 1.3 % and the total head within 0.9 %.
Remaining difference
In fully turbulent flow with water both friction factors are close. The small rest comes from the friction correlation and the pipe roughness, which the project assumes. BoreTherm’s reported pump power covers the field loss with a pump efficiency, so the fluid power above is computed from the total head and the flow for a like-for-like comparison.
BoreTherm features exercised
- Hydraulics and pressure drop
- Borehole layouts
- Heat pump selection: requirement sheet with the brine pump head