BoreTherm / Published referencesReference R8 / R9
Published reference · Hydraulics

Chiasson, Example 10.2: pressure drop of a 32-borehole field

A 4 × 8 field with water in reverse return. The U-tube loss is calculated; the mains, headers and fittings are carried as a header pressure drop.

11,243U-tube Reynolds number (book 1.13 × 10⁴)
33.0 kPaBoreTherm pump head
33.4 kPaBook pump head (11.16 ft)
−0.9 %Difference in pump head
01 / Project

Source, inputs and purpose

Source. Chiasson, A.D. (2016). Geothermal Heat Pump and Heat Engine Systems: Theory and Practice. Wiley / ASME Press. Example 10.1, pp. 290–292, and Example 10.2, pp. 292–294, with the branch and fitting sheets Figs. E.10.2b and E.10.2c (p. 294).

Inputs and reference results are taken from the cited publication; BoreTherm results were calculated with BoreTherm on the project rebuilt from those inputs; differences are explained below.

What the example checks

The pressure drop of a larger field with water in fully turbulent flow, along the path to the farthest borehole, and the fluid power the circulation pump must deliver.

Inputs

Values marked Assumption are not given in the book and were chosen for the BoreTherm project; the others are the book’s, with the section or page.

InputValueSource
Field32 boreholes, 4 × 8 at 20 ft (6.1 m), 250 ft (76.2 m) deepEx. 10.1
Flow160 gpm in total (10.09 L/s), 5 gpm per borehole; four circuits in reverse returnEx. 10.2
U-tubes and fluid1 in. SDR 11; water at 50 °F (10 °C)Ex. 10.2
Book path to the farthest boreholeU-tube branch with 20 ft of lateral (520 ft): 8.55 ft pipe + 0.14 ft fittings; headers and mains: 2.48 ftFig. E.10.2b
Header pressure drop in the project2.48 + 0.14 + 0.33 ft (the lateral) = 2.95 ft = 8.8 kPafrom Fig. E.10.2b
Pipe roughness1 µmAssumption
Thermal sideground and loads of Example 6.5 scaled to this field, Rb 0.15 m·K/W (they only illustrate)Assumption

Run the example in BoreTherm

  1. Open the 32-borehole pressure drop reference project from the examples folder (File → Open).
  2. Press Calculate, open Design → Heat pump → Selection results and click Calculate equipment requirements for the requirement sheet.
02 / How BoreTherm calculates it

How the pump head adds up

1 Flow per borehole160 gpm / 32 = 5 gpmwater at 10 °C2 ReynoldsRe 11,243 in 1 in. SDR 11:turbulent3 U-tube loss2 × 76.2 m→ 24.2 kPa4 Headermains, headers, fittings,lateral → 8.8 kPa5 Pump head24.2 + 8.8→ 33.0 kPa33.0 kPa (book 33.4 kPa, −0.9 %); fluid power 333 W
The path to the farthest borehole of the reverse-return field.
  1. Flow per boreholeReverse return gives every borehole the same flow.
  2. ReynoldsFully turbulent: the friction factors of the book and BoreTherm are close.
  3. U-tube lossBoreTherm's field pressure drop over twice the borehole length.
  4. HeaderThe book's mains, headers, fittings and lateral entered as the header pressure drop.
  5. Pump headThe sum, and with the flow the fluid power.
03 / In BoreTherm

The example in BoreTherm

Design → Field layout: the 4 × 8 field at 6.1 m.
Design → Field layout: the 4 × 8 field at 6.1 m.
Design → Heat pump → Selection results: brine flow and pump head.
Design → Heat pump → Selection results: brine flow and pump head.
04 / Results

Calculated results

Displayed values are rounded. Differences are BoreTherm relative to the book unless stated otherwise.

QuantityBookBoreThermDifference
U-tube Reynolds number1.13 × 10⁴11,243−0.5 %
U-tube pipe loss over 500 ft8.55 ft × 500 / 520 = 24.6 kPa24.2 kPa−1.3 %
Header, mains, fittings and lateral2.95 ft = 8.8 kPainput–
Total pump head11.16 ft = 33.4 kPa33.0 kPa−0.9 %
Fluid power0.45 hp = 336 W33.0 kPa × 10.09 L/s = 333 W−0.6 %
05 / Discussion

Why the results differ

Mapping the book’s path

BoreTherm’s field pressure drop is the U-tube loop over twice the borehole length. The book’s U-tube branch also contains 20 ft of lateral to the header (520 ft in total). The project therefore moves the lateral’s share, together with the headers, mains and fittings, into the header pressure drop of the heat pump selection. On the same 500 ft, the U-tube losses agree within 1.3 % and the total head within 0.9 %.

Remaining difference

In fully turbulent flow with water both friction factors are close. The small rest comes from the friction correlation and the pipe roughness, which the project assumes. BoreTherm’s reported pump power covers the field loss with a pump efficiency, so the fluid power above is computed from the total head and the flow for a like-for-like comparison.

BoreTherm features exercised