Published reference · Sizing

Chiasson, Examples 6.5 and 6.6: a 6 × 8 field with monthly loads and peaks

A 48-borehole field with monthly energies and monthly 6-hour peaks. The book limits the heat pump entering temperature; BoreTherm sizes on the mean fluid temperature.

4,083 mBoreTherm length, 48 × 85.1 m
4,661 mBook length, 48 × 97.1 m
−12.4 %Difference in total length
−0.07 °CLowest field outlet at the sized length
01 / Project

Source, inputs and purpose

Source. Chiasson, A.D. (2016). Geothermal Heat Pump and Heat Engine Systems: Theory and Practice. Wiley / ASME Press. §6.5.2: Example 6.5, pp. 212–213, and Example 6.6, pp. 213–214; input sheet Fig. 6.12 (p. 206), monthly loads Fig. 6.14 (p. 208), heat pump curve Fig. 4.22 (p. 130).

Inputs and reference results are taken from the cited publication; BoreTherm results were calculated with BoreTherm on the project rebuilt from those inputs; differences are explained below.

What the example checks

A larger, heating-dominated field (about 4 : 1) sized from monthly energies and monthly peak loads. The comparison shows how two treatments of the peaks and of the heat pump efficiency affect the length, and how a limit on the heat pump entering temperature translates to BoreTherm’s criterion on the mean fluid temperature.

Inputs

Values marked Assumption are not given in the book and were chosen for the BoreTherm project; the others are the book’s, with the section or page.

InputValueSource
Field6 × 8 = 48 boreholes at 6 m, 127 mmFig. 6.12
Ground2.0 W/(m·K), 2,200 kJ/(m³·K), 12 °CFig. 6.12
Borehole resistance0.15 m·K/W, imposed as Rb*Fig. 6.12
Fluidspecific heat 3.90 kJ/(kg·K), 432 L/min in totalFig. 6.12
Loadsheating 263.0 MWh/a, cooling 64.8 MWh/a; peaks 144 kW and 70 kW, 6 h each monthFig. 6.14
Heat pump curveheating COP 3.00 / 3.73 / 4.46 at 0 / 10 / 20 °C enteringFig. 4.22
Design period20 years from JanuaryEx. 6.5
Limits on the heat pump entering temperature0 °C and 30 °CEx. 6.5
Efficiencyfixed seasonal performance factor 3.5 heating, 5.5 cooling (the book recomputes the ground loads from the curve each month)Assumption
Sizing criteriamean fluid temperature ≥ −1.78 °C and ≤ 31.43 °C, converted from the entering-temperature limits with the book’s Eq. 6.8 (p. 194) at the largest peaksAssumption
Fluid propertiesdensity 1,030 kg/m³, viscosity 4 mPa·s, freezing point −10 °C (only the heat capacity flow matters with an imposed resistance)Assumption

Run the example in BoreTherm

  1. Open the 6 × 8 reference project from the examples folder (File → Open).
  2. Press Size borehole length; Results → Required borehole length lists the inlet and outlet temperatures at the sized length.
  3. For Example 6.6, set the length to 90 m and press Calculate.
02 / How BoreTherm calculates it

Two ways to the length

BookLoadsmonthly energies, 6 hpeaks every monthHeat pump curveground loads recomputedfrom the entering TPeaksline source on top ofthe monthly stepsLengthentering T ≥ 0 °C→ 97.1 m4,661 mBoreThermLoadsmonthly energies, 6 hpeaks every monthFixed SPF3.5 heating, 5.5 cooling(from the book's energy)Field g-functionfor months and peaks,48 boreholesSizingmean Tf ≥ −1.78 °C→ 85.1 m4,083 m (−12.4 %)
The peak treatment and the efficiency model differ; the entering-temperature limit is converted.
  1. Same loadsMonthly energies and monthly 6-hour peaks of Fig. 6.14.
  2. EfficiencyThe book recomputes the ground loads from the heat pump curve every month; BoreTherm uses a fixed seasonal factor.
  3. PeaksLine source in the book, the field g-function in BoreTherm.
  4. CriterionThe book limits the entering temperature; BoreTherm the mean fluid temperature, converted with the book's own relation.
03 / In BoreTherm

The example in BoreTherm

Design → Loads: monthly energies and peaks of Fig. 6.14.
Design → Loads: monthly energies and peaks of Fig. 6.14.
Results → Required borehole length: 85.1 m per borehole.
Results → Required borehole length: 85.1 m per borehole.
04 / Results

Calculated results

Displayed values are rounded. Differences are BoreTherm relative to the book unless stated otherwise.

QuantityBookBoreThermDifference
Ex. 6.5: required total length, heating limited4,661 m (48 × 97.1 m)4,083 m (48 × 85.1 m)−12.4 %
Same, BoreTherm’s classic-method sizing options4,661 m4,075 m (48 × 84.9 m)−12.6 %
Lowest field outlet (the book’s entering temperature) at the sized lengthlimit 0 °C−0.07 °Csupports the limit conversion
Sensitivity: fixed heating SPF 3.0 / 3.73 instead of 3.54,661 m3,715 / 4,218 m−20 % / −9.5 %
Ex. 6.6: the field drilled to 90 mentering temperature slightly below 0 °C near year 20mean fluid −1.13 °C in year 20 (limit −1.78 °C), lowest outlet +0.57 °CBoreTherm: still within the limit
05 / Discussion

Why the results differ

Why BoreTherm is shorter

Two modelling choices differ. The book superposes each month’s 6-hour peak as a line source on top of the monthly steps, while BoreTherm uses the field g-function for the peaks as well. The book also recalculates the ground loads every month from the heat pump curve, so the extraction rises as the entering temperature falls. BoreTherm uses a fixed seasonal performance factor here. The value 3.5 is the one implied by the book’s own 20-year heat pump energy (1.750 × 10⁶ kWh, p. 213). Fixed values of 3.0 and 3.73, the curve at 0 °C and 10 °C, bracket the result between −20 % and −9.5 %. The size and direction of the difference are similar to the moderate Kavanaugh cases.

Entering temperature against mean fluid temperature

The book states its limits on the heat pump entering temperature, which is the field outlet. BoreTherm sizes on the mean fluid temperature, so the project converts the limits with the book’s own relation between the two at the largest peaks. At the sized length BoreTherm’s lowest field outlet is −0.07 °C, next to the book’s 0 °C, which supports the conversion.

BoreTherm features exercised