3. Ground model

3.1 Assumptions

The ground is a homogeneous, isotropic semi-infinite solid with constant thermal properties, or a stack of horizontal layers (Section 3.3, Chapter 11). Heat is transported by conduction and, optionally, by a uniform horizontal groundwater flow (Chapter 12); freezing of pore water is not modelled. The ground surface is held at its undisturbed temperature; the boreholes are vertical unless inclined (Chapter 13). Because the heat equation is then linear, the temperature response to any load history is the superposition of step responses; all of BoreTherm's temperature calculations rest on this property.

3.2 Diffusivity and undisturbed temperature

α=λCv
(3.1)

The undisturbed ground temperature seen by a borehole is the mean over its length of the initial temperature field T(z)=Ts+qgeoz/λ. As in the classic monthly method, it is evaluated at half the borehole length:

Tm=Ts+qgeoλH2
(3.2)

The classic monthly method has no buried-depth input, and (3.2) deliberately uses H rather than D+H/2, as its published manual states (the value of 10.08 °C of the manual's worked example is reproduced). For a field of unequal lengths H is the mean length. For the example (Ts = 9 °C, qgeo = 0.06 W/m², λ = 2.6 W/(m K), H = 150 m) (3.2) gives Tm = 10.73 °C. Since Tm grows with H, the maximum fluid temperature can increase with the borehole length (Section 9.4).

3.3 Layered ground

The ground can be described as horizontal layers from the surface down, each with a thickness hi, a conductivity λi and a heat capacity Ci; the last layer extends to infinity. In the effective-property model (the default for layered ground) the layers enter every part of the calculation through thickness-weighted means over the active length [D,D+H] of the borehole:

λeff=1H∑ihiλi,Ceff=1H∑ihiCi,αeff=λeffCeff
(3.3)

where hi is the part of layer i inside [D,D+H]. Around a borehole the heat flows radially, through all layers side by side, so the layers act as parallel conductances and the arithmetic mean is the consistent choice; stored heat adds in the same way. λeff replaces λ in (3.6) and in the multipole ground conductivity, αeff replaces α in ts and the g-function. The means are evaluated as λtop+∑ihi(λi−λtop)/H, so that equal layers and a single layer reproduce the homogeneous ground bit for bit. The undisturbed temperature has two models. The mid-depth model (default) is (3.2) with λeff:

Tm=Ts+qgeoλeffH2
(3.4)

It is exactly (3.2) for a homogeneous ground. The active-length average follows the geotherm through the layers: the geothermal flux is vertical and crosses the layers in series, so the undisturbed temperature at depth z is Ts+qgeoR(z) with the series resistance R from the surface, and Tm is its mean over the active length:

Tm=Ts+qgeoH∫DD+HR(z)dz,R(z)=∫0zdz′λ(z′)
(3.5)

R is piecewise linear, so the trapezoidal rule over the pieces of the layers inside [D,D+H] is exact. For a homogeneous ground (3.5) gives Ts+qgeo(D+H/2)/λ, the convention of an open-source sizing tool; it accounts for the buried depth and for poorly conducting cover layers, which (3.4) ignores. Sizing evaluates λeff, αeff and Tm again at every trial length, and the g-function cache (Section 9.3) adds a node wherever D+H crosses a layer interface, where these values have a kink.

Table 5. Layers of the layered office example (VDI 4640 values).
LayerDepth [m]λi [W/(m K)]Ci [MJ/(m³ K)]
Clay / silt, water saturated0 – 81.72.4
Sand, water saturated8 – 252.42.5
Claystone / siltstone25 – 802.22.3
Limestone80 – 1252.82.2
Granite125 – ∞3.42.4

For this ground and the borehole of the example (D = 4 m, H = 150 m), (3.3) gives λeff = 2.621 W/(m K) and Ceff = 2.315 MJ/(m³ K), close to the homogeneous example's 2.6 and 2.2. The mid-depth model gives Tm = 10.72 °C, the active-length average 11.07 °C: the clay cover and the buried depth raise the temperature below them. Sized to the same limits, the field needs 140.3 m per borehole with the active-length average, 143.1 m with the mid-depth model and 143.7 m on the homogeneous ground; at the sized lengths less of the granite lies inside the active length, so λeff is lower than at 150 m.

The effective model ignores the vertical heat flow between the layers and that a conductive layer takes more than its share of the heat. The segmented model splits the boreholes at the layer interfaces and gives each segment pair the properties of its layers in the finite line source; it keeps λeff, αeff and Tm as the reference values and changes only the g-function. Chapter 11 describes it together with the borehole sections (diameter, grout and insulation along the depth, independent of the layers) and the uniform-fluid-temperature boundary condition that goes with them.

3.4 Superposition

With Tm as the initial state, the borehole-wall temperature for a piecewise-constant heat rate per metre qi applied from ti−1 is

Tb(t)=Tm+∑iqi−qi−12πλg(t−ti−1ts),q0=0
(3.6)

where g is the step response defined in Chapter 4. Chapters 8 and 9 apply (3.6) on monthly and hourly time steps.